Troubleshooting continued- 
(In addition to instruction manual.)
 
LED Status 
Control Status 
Probable Cause 
Five flashes and three 
second pause. 
Thermostat well fault. 
1.  Damage to the 
thermowell wire. 
2. Thermowell 
sensor 
resistance out of 
range. 
3. Replace 
thermowell. 
4.  Verify control is not 
wet or physically 
damaged. 
5.  Turn set point knob to 
"OFF" position. Turn 
set point knob to 
"PILOT" position and 
light pilot. 
6.  Replace gas valve if 
five flash error 
persists. 
Six flashes and three 
second pause. 
Chamber temperature sensor 
out of specification. Possible 
short. 
1. Chamber 
temperature 
sensor out of 
calibration. 
2. Possible 
short. 
Seven flashes and 
three second pause. 
Gas valve electronic fault 
detected. 
1.  Verify control is not 
wet or physically 
damaged. 
2.  Turn set point knob to 
"OFF" position. Turn 
set point knob to 
"PILOT" position and 
light pilot. 
3.  Replace gas valve if 
seven flash error 
persists. 
Eight flashes and three 
second pause. 
False pilot flame present. 
Pilot valve stuck in open 
position. 
Ten flashes and three 
second pause. 
Insufficient combustion air 
detected. Reset system. 
Insufficient combustion air.