LG PQDSBC1 Manual De Propietario

Descargar
Página de 14
12
Dry Contact for Economizer
Due to our policy of continuous product innovation, some specifications may change without notification.  
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
General Mode (1 - 6) - continued
Fan Level Setting Mode (7, 8)
Power Save Mode (9, A)
CONTROL_MODE_SW
Setting
Input A
Input B
Operating Mode Description
4
OFF
OFF
Indoor unit stopped, locked
ON
OFF
Indoor unit stopped, locked
OFF
ON
Indoor unit prior operating condition maintained, unlocked
ON
ON
Indoor unit prior operating condition maintained, unlocked
5
OFF
OFF
Indoor unit prior operating condition maintained, locked
ON
OFF
Indoor unit prior operating condition maintained, locked
OFF
ON
Indoor unit prior operating condition maintained, locked
ON
ON
Indoor unit prior operating condition maintained, unlocked
6
OFF
OFF
Indoor unit prior operating condition maintained, locked
ON
OFF
Indoor unit prior operating condition maintained, locked
OFF
ON
Indoor unit prior operating condition maintained, locked
ON
ON
Indoor unit operating, unlocked
CONTROL_MODE_SW
Setting
Input A
Input B
Operating Mode Description
7
OFF
OFF
Indoor unit fan operating at low level, locked
ON
OFF
Indoor unit fan operating at low level, unlocked
OFF
ON
Indoor unit stopped, locked
ON
ON
Indoor unit stopped, unlocked
8
OFF
OFF
Indoor unit fan operating at low level, locked
ON
OFF
Indoor unit fan operating at low level, unlocked
OFF
ON
Indoor unit stopped, locked
ON
ON
Indoor unit operating condition maintained, unlocked
CONTROL_MODE_SW
Setting
Input A
Input B
Operating Mode Description
9
OFF
OFF
Indoor unit operating in power save mode, locked
ON
OFF
Indoor unit operating in power save mode, unlocked
OFF
ON
Indoor unit stopped, locked
ON
ON
Indoor unit operating not in power save, unlocked
A
OFF
OFF
Indoor unit operating in power save mode, locked
ON
OFF
Indoor unit operating in power save mode, unlocked
OFF
ON
Indoor unit stopped, locked
ON
ON
Indoor unit stopped, locked
INSTALLATION