Remote Thermostat Control
Multiple Units Connected to One Remote
Thermostat (2200 Series)
One remote control thermostat may be used to control
multiple resistance heat Zoneline units, however the units
may not be wired direct. Since each Zoneline unit has an
integral transformer, direct wiring can result in a “bucking”
Remote Control (Low Voltage) Wiring
One stage Thermostat Controlling Three Zoneline Units
Resistance Heat Zoneline 2200 Series Units
(Not Applicable on Heat Pump Units)
or “boosting” voltage condition, and is in violation of the
National Electric Code. The diagram below shows the
correct wiring for such an installation through the use of
field supplied isolation relays.
NUMBER OF
UNITS CONTROLLED
2
3
4
MORE THAN 4
FIELD SUPPLIED RELAY SPECIFICATIONS
RELAY DESIGNATION
R1, R2, and R3
POTTER and BRUMFIELD TYPE KA11AY-24 OR EQUIVALENT
POTTER and BRUMFIELD TYPE KA14AY-24* OR EQUIVALENT
POTTER and BRUMFIELD TYPE KU17A11-24* OR EQUIVALENT
USE COMBINATION OF RELAYS SPECIFIED ABOVE
NOTE: Current draw through thermostat contacts should not exceed 1.0 amps.
*Special order, 100 piece minimum order.
Transformer
18 Va MIN