GE RAG61 Instruccion De Instalación

Descargar
Página de 60
55
Model Number
Fan Motor- 230 Volts
Fan Motor- 208 Volts
Model Number
Fan Motor - 265 Volts
Maximum Connected Load For
Premium Series (5200)
The maximum connected load of a Zoneline unit occurs
when the unit is in resistance heating operation. To
determine the maximum amperage draw or wattage
consumption of the unit: First, find the chassis model
number in TABLE A and read the amperage or wattage of
the unit in the appropriate column; Second, find the power
connection kit to be used in TABLE B and read the
amperage or wattage of the heater in the appropriate
column.
The sum of the fan motor requirements TABLE C and the
heater requirements TABLE D equal the Maximum
Connected Load of the unit.
Table  C
Heating Operation - Indoor Fan Motor Electrical Data
Watts
Amps
Watts
Amps
Watts
Amps
AZ52H07DAB/DAD*
25
0.1
20
0.1
AZ52H07EAB/EAD*
30
0.1
AZ52H09DAB/DAD*
25
0.1
20
0.1
AZ52H09EAB/EAD*
30
0.1
AZ52H12DAB/DAD*
25
0.1
20
0.1
AZ52H12EAB/EAD*
30
0.1
AZ52H15DAB/DAD*
45
0.2
40
0.2
AZ52H15EAB/EAD*
50
0.2
Outdoor Fan Motor Electrical Data
Two Fan Motor Models
For Information Only. Do Not Include In Maximum Connected Load Calculations.
Model Number
Fan Motor- 230 Volts
Fan Motor- 208 Volts
Model Number
Fan Motor - 265 Volts
Watts
Amps
Watts
Amps
Watts
Amps
AZ52H07DAB/DAD
65
0.3
60
0.3
AZ52H07EAB/EAD
75
0.3
AZ52H09DAB/DAD
65
0.3
60
0.3
AZ52H09EAB/EAD
75
0.3
AZ52H12DAB/DAD
90
0.4
80
0.4
AZ52H12EAB/EAD
100
0.4
AZ52H15DAB/DAD
135
0.6
125
0.6
AZ52H15EAB/EAD
135
0.5
Table  D
Heating Operation - Resistance Heater Electrical Data
Heater - 230 Volts
Heater - 208 Volts
Heater - 265 Volts
Power
Connection
Kit
Power
Connection
Kit
Watts
Amps
Watts
Amps
Watts
Amps
RAK3152
2550
11.1
2085
10.0
RAK5152
1700
6.4
RAK3202
3450
15.0
2820
13.6
RAK5172
3000
11.3
RAK3302
5000
21.7
4090
19.7
RAK5202
3700
14.0
RAK5302
5000
18.9
* These models have 2 fan
motors. Information shown is
for the indoor fan motor only.