Analogue Signal Processing
FP0 Analogue Units
Item
Description
Rated operating voltage
Operating voltage range
24VDC
21.6 to 26.4VDC
Rated current consumption
FP0-A80: 60mA or less, FP0-A21/A04V: 100mA or less, FP0-A04I: 130mA or less
Ambient temperature
0°C to + 55°C
Storage temperature
-20°C to + 70°C
Size
90 x 25 x 60mm
Weight
Approximately 100g
General specifications
 
FP0-A21 
FP0-A04V 
FP0-A04I
 
1  
   
 4 
 
 
             4
0 to 20mA:   
0 to 20mA: K 0 to K 4000    
 
 
 
 
 
-10V to +10V:  
-10V to +10V: K -2000 to K+2000  
 
 
12 bits (1/4000)
 
500ms 
500µs 
   500µs
1% for full-scale (0 to 55°C), 0.6% for full-scale (at 25 °C)
 
 
 
 
 
Voltage mode: less than 0.50
Ω 
 
 
-
 
 
 
 
 
    Voltage mode: +/- 10mA   
 
 
-
 
 
          Less than 300
Ω 
 
 
            1000
Ω or more 
 
 
      Less than 500
Ω
Optical coupler insulation between analogue output terminal and FP0 internal circuit
 
 
DC/DC converter insulation between analogue output terminal and analogue I/O unit external power supply
 
 
    DC/DC converter insulation between analogue output terminal and analogue input terminal
 
 
16 output points  
 
 
32 output points 
 
 
32 output points
Analogue output specification
Item
Product
                 Description
 
  FP0-A21 
FP0-A80
Number of channels
Input range selectable
( 2 CH)
2 channels/unit
8 channels / unit
-100 to +100mV / 0 to 5V / -10V to +10V
0 to 20mA
2ms / channel
Voltage mode 
 
   0 to 5V / -10V to +10V
Digital output
Resolution
Conversion speed
Overall accuracy
Input impedance
Maximum input
Insulation
FP0 input address
*
1
 K means decimal constants.
*
2
 Reference temperature → Reference points is start points.
*
3
 Reference temperature → Reference points is end points.
*
4
 The address varies depending on the position of the analogue unit. (WX2/3, WX4/5 or WX6/7)
Current mode 
 
   0 to 20mA
Thermocouple mode 
K, J, T type thermocouple
 
K up to 1000°C   or   -100°C to terminal temperature (selectable)
 
J up to     750°C   or   -100°C to terminal temperature (selectable)
 
T up to     350°C   or   -100°C to terminal temperature (selectable)
0 to 5V / 0 to 20mA:  
 
K 0 to K 4000 (H 0000 to H 0FA0) 
 *
1
 
-10 to +10V (-100 to +100mV): 
K -2000 to K +2000 (HF830 to H07D0)
Thermocouple: The value of broken wire detection is K 20000.
 
For plus:  
K temperature of terminal *
2
  to K 1000 (Unit is Celsius)
 
For minus:   K-100 to K temperature of terminal *
3
  (Unit is Celsius)
            12 bits (1/4000)
Voltage/current mode: 
1ms/ channel
Thermocouple mode: 
560ms/ channel
 
 
 
Voltage/current mode: 
1% for full-scale (0 to 55°C), 0.6% for full-scale (at 25°C)
Thermocouple mode: 
 Offset error (0 to 55°C),   2% for full-scale (K-type)
2.7% for full-scale (J-type)
5.8% for full-scale (T-type)
 
 
Linearity error (0 to 55%): 1% for full scale
Voltage mode: 1M ohm or more
Current mode: 250ohm
Voltage mode: +/- 15V
Current mode: +30mA
Optical coupler insulation between analogue input terminal and FP0 internal circuit
(No insulation between analogue inputs)
DC/DC converter insulation between analogue input terminal and analogue I/O unit external power supply
DC/DC converter insulation between analogue input terminal and analogue output terminal
32 input contact points:   First 16 points analogue input CH0 data (WX2) *
4
Last 16 points analogue input CH1 data (WX3) *
4
32 input contact points: 
First 16 points analogue input 
CH0, 2,4,6 data (WX2) *
4
Last 16 points analogue input 
CH1,3,5,7 data (WX3) *
4
Analogue input specification
Item
Description
4 to 20mA
 -10V to +10V
K -2000 to K+2000
K 0 to K 4000
Product
Number of channels
Output signal selectable
Digital input *
1
 
Resolution
Conversion speed
Overall accuracy
Output impedance
Maximum output current
Allowable output load 
resistance
Insulation
Reserved CPU addresses *
4
Voltage mode 
-10V to +10V  
 
 
                
 
 
 
Current mode 
0 to 20mA 
 
 
 
 
 
 
 
07/2007