D9412GV3/D7412GV3 | Program Entry Guide | 1.0  Introduction 
EN | 11 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
Table 3:  UL 864 Programming Requirements (continued) 
 
Product Feature/Option  Permitted in 
UL 864? (Y/N) 
Possible Settings  Settings Permitted in  
UL 864 
Refer to 
Page: 
For IP Communications to a D6600 Receiver 
Enhanced Comm 
Yes 
Yes / No 
Set to Yes 131 
Path1 IP Add1 (2, 3 or 4) 
Yes 
000 to 255  
Program a valid IP 
address 
131 
Path 1 Poll Rate 
Yes 
0, 5 to 65535 sec*  Program as necessary 
132 
Path 1 Ack Wait 
Yes 
0, 5 to 65535 sec*  Program as necessary 
135 
Path 1 Retry Count 
Yes 
0 to 255 
Program as necessary 
135 
SDI 88 Supervision 
Yes 
Yes / No 
Set to Yes 136 
For Ground Fault Enable Switch 
(Refer to the 
D9412GV3/D7412GV3 
Operation and Installation 
Guide
 (P/N: 
F01U143070) 
Yes 
Closed = Enabled 
Open = Disabled 
Closed N/A 
* Set the Path 1 Poll Rate to 65535 for 24 hr. 
The following programmable parameters are recommended by Bosch when installing a commercial fire alarm 
system. Always check with your local Authority Having Jurisdiction.  
Table 4:  UL 864 Programming Recommendations 
 
Prompt Possible 
Settings 
Recommendation 
Phone Line Fail Report 
Yes / No 
Yes 
Phone Line Restoral Report 
Yes / No 
Yes 
Fire Walk Start Report 
Yes / No 
Yes 
Fire Walk End Report 
Yes / No 
Yes 
Cancel Report 
Yes / No 
Yes 
CC# Scope 
Panel Wide, Account Wide, Area 
Wide, Custom, No Keypad 
Do not program No Keypad 
CC# Enhanced Command 
Center 
Yes / No 
Set to Yes, if applicable 
CC# Menu Key Lock 
Yes / No 
If using D1256RB, set to No 
Reset Sensors 
Disable/Enable/Passcode Protect 
Enable 
Fire Test 
Disable / Enable / Passcode Protect  Enable 
L## Reset Sensors 
Disable / Enable 
If Reset Sensor is set to Passcode 
Protect
, set this to Enable 
L## Fire Test 
Disable / Enable 
If Fire Test is set to Passcode 
Protect
, set this to Enable 
U### User Group 
0 to 8  
Program as 0 
P## Ring Until Restored 
Yes / No 
May be required for Waterflow
otherwise No 
P## Cross Point 
Yes / No 
Set to No for Fire devices. 
D# Fire Unlock 
Yes / No 
No