D9412GV3/D7412GV3 | Program Entry Guide | 4.0  Schedules (Skeds) 
EN | 120 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
Default: 
Selection:  0 to 24, 28, 29 
 
 
 
  S## Access Ctl Level # 
 
Default: No 
Yes 
Turn off access for 
level #. 
17 
Access Control Level Off: 
This function emulates the 
ACCESS CMD LEVEL 
command that determines 
whether a user’s token or card 
level is disabled. This function 
allows access to be turned off 
for the levels programmed. 
Selection: Yes or No 
The first parameter enables the sked 
to turn off access for Levels 1 through 
14. 
No 
Do not turn off 
access for level #. 
 
 
 
  S## Door 1 [through 8] 
 
Default: No 
Yes 
Unlock Door #. 
18 
Unlock Door: This function 
emulates the UNLOCK? 
12345678 keypad function for 
unlocking a door. 
Selection: Yes or No 
Enable the sked to unlock the doors 
programmed Yes
No 
Do not unlock 
Door #. 
 
 
 
  S## Door 1 [through 8] 
 
Default: No 
Yes 
Secure Door #. 
19 
Secure Door: This function 
emulates the SECURE? 
12345678 keypad function for 
securing a door. 
Selection: Yes or No 
Enable the sked to return the doors 
programmed Yes to the secured 
state. 
No 
Do not secure 
Door #. 
 
 
 
  S## Door 1 [through 8] 
 
Default: No 
Yes 
Lock Door #. 
20 
Lock Door: This function 
returns an unlocked (Function 
18) or secured (Function 19) 
door to a normal locked door 
state. 
Selection: Yes or No 
Enable the sked to lock the doors 
programmed as Yes and return them 
to the normal Door Mode. 
No 
Do not lock Door 
#. 
 
 
 
  S## Door 1 [through 8] 
 
Default: No 
Yes 
Enable the 
sending of Access 
Granted Events 
for Door #. 
21 
Access Authority Events 
On:
 The control panel can log 
Access Granted Events when 
a valid token, RTE, REX, or 
Unlock Door event is detected 
for a specific door. These 
events can be directed to print 
at a local printer or send a 
report remotely through phone 
routing. This sked enables 
Access Granted Events to be 
reported for Door #. 
Selection: Yes or No 
This parameter enables the sending 
of Access Granted Events for Door #. 
No 
Do not enable the 
sending of Access 
Granted Events 
for Door #. 