D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 42 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
A# Fire Time 
Default: 
6 min 
Selection: 
1 min to 90 min 
Enter the number of minutes the bell rings for Fire 
Alarm points. The relay activated for this time is 
programmed in A# Fire Bell in Area Relays. 
The bell output begins as soon as the fire alarm 
occurs. It shuts off the bell when the programmed 
number of minutes expires. 
If programmed for 1 min, the output can be anywhere 
from 0 to 60 sec of bell time. Program Fire Time for 2 
min or more to ensure you have ample output time. 
 
 
To meet UL 864 requirements, program 
A# Fire Time for at least 5 min. Check 
with your AHJ to determine the 
appropriate bell time for your 
geographical area. 
 
A# Fire Pattern 
Default: 
Pulse 
Selection: 
Steady, Pulse, CaStnd, TmCod3 
Steady Steady 
Output 
Pulse Pulse 
March 
Time 
120 beats per minute, at an even 
tempo 
CaStnd California 
Standard 
10 sec On + 5 sec Off + 10 sec On + 
5 sec Off. This sequence repeats 
until bell time expires. 
TmCod3 
Temporal Code 3 
0.5 sec On, 0.5 sec Off, 0.5 sec On, 
0.5 sec Off, 0.5 sec On, 1.5 sec Off; 
pattern repeats. This sequence 
repeats for a minimum of 3 min and 
with a ± 10% tolerance. 
Select the bell pattern this area uses to signal an 
alarm on a Fire point. 
When an alarm occurs on two Fire 
points sharing the same relay, the bell 
pattern of the most recent fire event 
takes precedence. 
A# Burg Time 
Default: 
6 min 
Selection:  1 to 90 min (in one-minute 
increments) 
 
 
4 min for UL 
5 min for ULC 
Enter the number of minutes the bell rings for 
Burglary Alarm points. The relay activated for this 
time is programmed in A# Alarm Bell in Area Relays. 
The bell output begins as soon as the burglary alarm 
occurs. It shuts off the bell when the programmed 
number of minutes expires. 
When the control panel’s internal clock begins a new 
minute, it considers the first minute expired. Program 
Burg Time for 2 min or more. 
Check with your AHJ to determine the 
appropriate bell time for your 
geographical area. 
For SIA CP-01 Compliance: 
A# Burg Time
 must be 6 min or more. 
A# Burg Pattern 
Default: 
Steady 
Selection: 
Steady, Pulse, CaStnd, TmCod3 
Select the bell pattern this area uses to signal an 
alarm on a Non-fire point.