2-Series Integrated Control Processor 
 
Crestron CP2/CP2E
 
Uploading Touchpanel Projects via the CP2/CP2E 
You can use a connection to the CP2 or CP2E to upload VisionTools Pro-e projects 
to any Cresnet touchpanel. Compiled projects for TPS panels are contained in VTZ 
files; projects for all other touchpanels are contained in HEX files.  
Before uploading, open Viewport and click Diagnostics | Report Network Devices 
to verify that the touchpanel is being detected by the control system. (As with any 
network device, touchpanels must be identified by unique hexadecimal network IDs. 
These IDs are set in the SIMPL Windows program.) 
To upload a project: 
1.  From VT Pro-e: Click the Project | Upload  button 
 on the toolbar, 
or click File | Upload Project. 
 
From Viewport: Click  File Transfer | Send Touchpanel or press 
Alt+T
2.  Select the network ID of the touchpanel, as set in SIMPL Windows, 
from the drop-down list. 
3.  Browse to the HEX or VTZ file to be uploaded. If the file is a HEX 
file, click Open to begin the transfer.  
 
If the file is a VTZ file, choose the pages to send to the TPS panel. The 
choices are as follows: 
All Files in Project: sends the entire project. 
Only Changed Files: sends only the files that are different 
from those that are currently stored in the panel. Note that if 
any pages in the panel are not present in the project, those 
pages will be deleted from the panel. 
- Additional 
choices 
include 
Do not send graphic files and Do 
not send sound files. These are often very large files that need 
not be reloaded with every transfer. 
Updating the Operating System 
As with all 2-Series control systems, operating system files for the CP2 and CP2E 
have a .cuz extension. You can obtain .cuz updates (when available) from the 
software downloads area of the Crestron website. To download an update, click the 
.cuz file and choose the Save to Disk option, then specify the directory where the 
update will be stored. 
NOTE: In some cases Microsoft's Internet Explorer may append a .zip extension to a 
downloaded .cuz file. For example, a file called "C2-1008.cuz" may appear as "C2-
1008.cuz.zip." If this happens, rename the file, removing the .zip extension. 
To upload the new .cuz to the control system: 
1.  Open Viewport and select File | Update Control System.  
2.  Browse to the .cuz file and click Open to start the transfer. 
26  
  2-Series Integrated Control Processor: CP2/CP2E 
Operations Guide - DOC. 5980