CH.2:  TIU050                                                  06 Apr 2000                                                         PAGE 17
GFK-1819
Pull-up and Pull-down switches are used to increase the signal level on the RS-485 bus.  This is useful if
there is a long bus and a significant amount of attenuation is anticipated.
Termination resistance of 120
Ω
 must be placed across each end of the RS-485 bus.  With switch 2 ON,
a 120
Ω
 resistance is placed across the bus. This is only used if the TIU050/100/110 is the last device at
either end of the bus.
2.5 TIU050 
Dimensions
TOLERANCES ARE +/- 0.01” [0.3mm] UNLESS STATED OTHERWISE
TIU050 CUTOUT DETAILS
3.27”       [83     mm]
+ 0 .0 2
-0 .0 0
+ 0 .5
-0 .0
5.95” [151m m]
UP TO 0.04”[1mm] CORNER
RADIUS IS ACCEPTABLE
Figure 2.5 – TIU050 Cutout