PAGE 30                                                         06 Apr 2000                             CH. 5: TIU200/201/202/203
GFK-1819
5.5.1 
TIU20X Configuration of the RS-485 Port
The configuration bank (shown in Figure 2.23) sets the parameters of the RS-485 port as described in
Table 5.1.
Table 5.1 – Configuration Bank
Switch 1
ON: Pull-up (must be used together with switch 3)
OFF: no Pull-up
Switch 2
ON: 120
Ω
 termination
OFF: no termination
Switch 3
ON: Pull-down (must be used together with switch 1)
OFF: no Pull-down
Switch 4
Reserved for future use
NOTE: Switch 1 and 3 must be used together.  Either both pull-up and pull-down are
used or neither is used.
Pull-up and Pull-down switches are used to increase the signal level on the RS-485 bus.  This is useful if
there is a long bus and a significant amount of attenuation is anticipated.
Termination resistance of 120
Ω
 must be placed across each end of the RS-485 bus.  With switch 2 ON,
a 120
Ω
 resistance is placed across the bus. This should only be used if the TIU050/10X/11X/20X is the
last device at either end of the bus.
5.6 TIU20X 
Dimensions
Figure 5.8 – TIU20X Cutout
72/(5$1&(6 $5(  µ >PP@ 81/(66 67$7(' 27+(5:,6(
7,8; &87287 '(7$,/6
µ
>
PP@
+0.02
-0.00
+0.5
-0.0
µ > PP@
83 72 µ &RUQHU >5$',86 ,6 $&&(37$%/(PP@
+0.02
-0.00