LP Gas Hook Up
Vent the enclosure for an LP gas cylindar with openings at the level of 
the cylinder valve and at the floor level. 
Ensure one side of the enclosure is completely open.
For enclosures that have four sides, complete with a top and bottom:
At least two ventilation openings at cylinder valve         less than 
• 
one square inch per pound (7.1 cm²/kg) of stored fuel capacity and 
not less than a total free area of 10 square inches (64.5cm²). If 
ventilation openings at floor level are in a sidewall, there shall be 
at least two openings. The bottom of the openings shall be at floor 
level and the upper edge no more than 5 inches (127 mm) above 
the floor. The openings shall be equally sized, spaced at 180º (3.14 
rad) and unobstructed.
Every opening shall have minimum dimensions so as to permit the 
• 
entrance of a 1/8 inch (3.2 mm) diameter rod.
Transporting and Storing LP Gas
Place the dust cap on the cylinder valve outlet whenever the cylinder is 
not in use. Only install the type of dust cap on the cylinder valve outlet 
that is provided with the cylinder valve. Other types of caps or plugs 
may result in leakage of propane.
Transport only one cylinder at a time. Ensure the cylinder is secured in 
an upright position with the control valve turned off and the dust cap 
in place. Store cylinders outdoors and out of reach of children. Do not 
store cylinders in a building, garage, or any other enclosed area.