Honeywell MS4103 Manual De Usuario

Descargar
Página de 268
41
Actuator Features
Fail Safe
Actuator O.S. Number
MS4110A1002  MS4110A1200
MS7520A2007  MS7520A2205  MS7520H2208
MS8120A1007  MS8120A1205
MS4120A1001  MS4120A1209
Power Supply 
Voltage 100-250 Vac
24 Vac
24 Vac
100-250 Vac
Frequency
60 Hz
50 / 60 Hz
50 / 60 Hz
60 Hz
Power
45 VA
16 VA
40 VA
60 VA
Actuator Torque 
(lb.-in.)
88
175
175
175
Linkage Stem Force 
(lbs.)
117
234
234
234
Control 
(0)2-10 Vdc
4-20 mA (external 500 Ohm Resistor)
Floating
Two-Position SPDT
Two-Position SPST
Fail Safe Action
 Configurable 
Open/Closed
 Configurable 
Open/Closed
 Configurable 
Open/Closed
 Configurable 
Open/Closed
Normal Position (no signal)  (field configurable) Stem Up/Down Stem Up/Down Stem Up/Down Stem Up/Down
Actuator Stroke  
(inches)
95°
95°
95°
95°
Timing 
(seconds at 0.75" stroke)
90
90
90
90
Aux Switch 
SPDT Built In
0 / 2
0 / 2 / 2
0 / 2
0 / 2
2 x SPDT Add-On
SW2-US
SW2-US
SW2-US
SW2-US
Feedback 
2-10 Vdc Built In
Valve 
Size 
(inches)
Cv
Max Static  
Water Pressure
Max Steam 
Pressure / 
Temperature
Flow  
Characteristic
Valve  
Action
Valve OS  
Number
Close-off Pressure, psid
2-W
ay 
 
W
ater V
alves
Straight 
Through
1/2"
0.73
217 psi @ 248 F
15 psi  
(2-position)
Equal %
Stem down to close
V5011N1008
230
230
230
230
1.16
Stem down to close
V5011N1016
230
230
230
230
1.85
Stem down to close
V5011N1024
230
230
230
230
2.9
Stem down to close
V5011N1032
230
230
230
230
2.9
Stem up to close
V5011N3004
230
230
230
230
4.7
Stem down to close
V5011N1040
230
230
230
230
4.7
Stem up to close
V5011N3012
230
230
230
230
3/4"
7.3
Stem down to close
V5011N1057
150
230
230
230
3/4"
7.3
Stem up to close
V5011N3020
150
230
230
230
1"
11.7
Stem down to close
V5011N1065
136
230
230
230
1"
11.7
Stem up to close
V5011N3038
136
230
230
230
1-1/4"
18.7
Stem down to close
V5011N1073
84
171
171
171
1-1/4"
18.7
Stem up to close
V5011N3046
84
171
171
171
1-1/2"
29.3
Stem down to close
V5011N1081
55
113
113
113
2"
46.8
Stem down to close
V5011N1099
30
63
63
63
2-1/2"
63
250 psi @ 100F
Stem down to close
V5011F1105
21
45
45
45
3"
100
250 psi @ 100F
Stem down to close
V5011F1113
13
27
27
27
2-W
ay 
 
Steam V
alves
Straight 
Through
1/2"
0.73
217 psi @ 248 F
100 psig / 
337 F
Linear
Stem down to close
V5011N2006
100
100
100
100
1.16
V5011N2014
100
100
100
100
1.85
V5011N2022
100
100
100
100
2.9
V5011N2030
100
100
100
100
4.7
V5011N2048
100
100
100
100
3/4"
7.3
V5011N2055
100
100
100
100
1"
11.7
V5011N2063
100
100
100
100
1-1/4"
18.7
V5011N2071
84
100
100
100
1-1/2"
29.3
V5011N2089
55
100
100
100
2"
46.8
V5011N2097
30
63
63
63
2-1/2"
63
250 psi @ 100F
V5011G1111
21
45
45
45
3"
100
250 psi @ 100F
V5011G1129
13
27
27
27
3-W
ay 
 
W
ater V
alves
Mixing
1/2"
2.9
217 psi @ 248 F
N / A
Linear B-AB / 
Equal % A-AB
Stem up closes A-AB
V5013N1030
230
230
230
230
1/2"
4.7
V5013N1048
230
230
230
230
3/4"
7.3
V5013N1055
150
230
230
230
1"
11.7
V5013N1063
136
230
230
230
1-1/4"
18.7
V5013N1071
84
171
171
171
1-1/2"
29.3
V5013N1089
55
113
113
113
2"
46.8
V5013N1097
30
63
63
63
VA
lV
e Selection
NPT Globe Valves ½- 3"
With Direct coupled Spring Return Actuators and Valve linkage
Q5020A1003 
Required