Graco 312964C Manual De Usuario

Descargar
Página de 20
Set Up
312964C
3
Set Up
Dipswitch Settings
The TLM has two, 4 - position dipswitches labeled S1 
and S2. TLM dipswitches must be set to match those of 
the transceiver the TLM will be communicating with. The 
factory default setting for all TLM’s is (‘1’ ‘1’). The first ‘1’ 
refers to the Network ID and the second ‘1’ refers to the 
Transceiver ID.
Network ID (S1): The RF identification setting 
assigned to a Matrix installation. All compo-
nents in the system use this same Network ID. 
For example, if one dealership is using Network 
ID (1), the dealership across the street would 
require Network ID (2, 3, 4, 5, 6, 7, or 8) to avoid 
RF interference between the two systems.
Transceiver ID (S2): The RF identification set-
ting assigned to a Matrix Transceiver(s). Matrix 
system components are then assigned to the 
Transceiver’s ID as desired for RF communica-
tion. For example, if a system required two 
Transceivers, some components would be 
assigned to one Transceiver and other compo-
nents would be assigned to the second Trans-
ceiver.
There are 8 Network ID's and 8 Transceiver ID's possi-
ble by changing the position of the dipswitches. The 
eight positions are identified as 1, 2, 3, 4, 5, 6, 7 and 8. 
See F
. 2 and F
IG
. 3 on pages 4 and 5.
Setting the S1 and S2 Dipswitches
(Unless otherwise indicated, for the following instruc-
tions Refer to F
IG
. 1 and F
1.
Remove the protective plastic over cover (5) on the 
TLM display that was used for shipping and discard. 
2.
Remove the four screws (3) holding the tank monitor 
cover (7) in place.
3.
Remove the cover (7).
4.
Remove the insulating foam (4) to access the circuit 
board.
5.
If installed, remove batteries (1).
6.
Set the S1 and S2 settings to match those of the 
transceiver that this TLM will communicate with 
(F
. 2 and F
IG
. 3).
Do not install or service this equipment unless you 
are trained and qualified. Installing and servicing 
this equipment requires access to parts which may 
cause fire, explosion, and serious injury if work is 
not performed properly. Read warnings, page 2.
Do not use the TLM with pressurized tanks.
NOTICE
Do not over tighten tank level monitor into tank 
bung! 
Over tightening can cause permanent dam-
age and result in inaccurate readings.
Do not use thread sealant or adhesive. Many of 
these products are chemically incompatible with the 
PC/ABS plastic.
Use the Graco-supplied down tube 15U731 only. Do 
not replace down tube with any other tube.
F
IG
. 1
NOTICE
Wait at least 30 seconds after the dipswitch settings 
are made before installing the batteries. If you do not 
wait the 30 seconds, the software will not recognize 
the new settings.
3
2
1
4
5
7