4.16.3 Reference of the terminal FM (pulse train output) and AM (analog voltage 
output) (Pr. 55, Pr. 56, Pr. 291, Pr. 866, Pr. 867)
(1) Pulse train output of the terminal FM (Pr. 291)
• Two types of pulse train can be output to the terminal FM.
Two types of monitor output, pulse train output from the terminal FM and analog voltage output from the terminal
AM, are available. In addition, pulse train output by voltage output and by open collector output can be selected
for terminal FM.
Set the reference of the signal output from terminal FM and AM.
Parameter 
Number
Name
Initial 
Value
Setting Range
Description
55 *
Frequency monitoring 
reference
60Hz
0 to 400Hz
Set the full-scale value to output the output frequency 
monitor value to terminal FM and AM.
56 *
Current monitoring 
reference
Rated 
inverter 
current
55K or 
lower
0 to 
500A
Set the full-scale value to output the output current 
monitor value to terminal FM and AM.
75K or 
higher
0 to 
3600A
291
Pulse train I/O 
selection
0
Pulse train input Pulse train output
0
Terminal JOG
FM output
1
Pulse train input FM output
10
Terminal JOG
High speed pulse train output (50%Duty)
11
Pulse train input High speed pulse train output (50%Duty)
20
Terminal JOG
High speed pulse train output (ON 
width is always same)
21
Pulse train input High speed pulse train output (ON 
width is always same)
100
Pulse train input
High speed pulse train output (ON 
width is always same)
The inverter outputs the signal input 
as pulse train as is
866 *
Torque monitoring 
reference
150%
0 to 400%
Set the full-scale value to output the torque monitor value 
to terminal FM and AM.
867
AM output filter
0.01s
0 to 5s
Set the output filter of terminal AM.
* The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr.
77 Parameter write selection.
FM output circuit
• When Pr. 291 Pulse train I/O selection = "0 (initial value) or 1",
FM output is selected and pulse train with maximum of
8VDC 2400pulses/s is output. 
The pulse width can be adjusted by calibration parameter C0
(Pr. 900) FM terminal calibration
 using the operation panel
and parameter unit. 
• Output frequency, etc. of the inverter can be indicated by
connecting a DC ammeter of full-scale 1mA, digital indicator,
etc.
*1 Not needed when the operation panel (FR-DU07) or parameter unit (FR-PU04
/FR-PU07
) is used for calibration.
Use a calibration resistor when the indicator (frequency meter) needs to be calibrated by a neighboring device because the indicator is
located far from the inverter.
Note that the needle of the frequency meter may not deflect to full-scale when the calibration resistor is connected. In this case, use this
resistor and perform calibration of operation panel or parameter unit.
*2 The initial setting is 1mA full-scale and 1440 pulse/s terminal FM frequency at 60Hz.
Inverter
24V
2.2K
20K
3.3K
SD
FM
8VDC
T2
T1
Pulse width T1: Adjust using calibration parameter C0
Pulse cycle T2: Set with Pr. 55 (frequency monitor)
Set with Pr.56 (current monitor)
(Digital indicator)
(-)
1440 pulses/s(+)
FM
SD
Indicator
1mA full-scale 
analog meter
(+)
1mA
FM
SD
 Calibration 
resistor
*1
(-)