292
Frequency/torque setting by analog 
4.21.4 Response level of analog input and noise elimination 
(Pr. 74, Pr. 822, Pr. 826, Pr. 832, Pr. 836, Pr. 849)
(1) Block diagram
Response level and stability of frequency reference command and torque reference command by analog input
(terminal 1, 2, 4) signal can be adjusted.
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
74
Input filter time constant
1
 0 to 8
The primary delay filter time constant for the analog input 
can be set. A larger setting results in slower response.
822
Speed setting filter 1
9999
0 to 5s
Set the time constant of the primary delay filter relative to 
the external speed command (analog input command).
9999
Pr. 74 used
826
Torque setting filter 1
9999
0 to 5s
Set the time constant of the primary delay filter relative to 
the external torque command (analog input command).
9999
Pr. 74 used
832
Speed setting filter 2
9999
0 to 5s, 9999 Second function of Pr. 822 (valid when RT terminal is on)
836
Torque setting filter 2
9999
0 to 5s, 9999 Second function of Pr. 826 (valid when RT terminal is on)
849
Analog input offset 
adjustment
100%
0 to 200%
This function provides speed command by analog input 
(terminal 2) with offset. Motor rotation due to noise, etc. 
by analog input can be avoided at zero speed command.
Terminal 1 (2, 4 ) input
RT-OFF
RT-ON
Pr. 822 = 9999
Pr. 822    9999
Pr. 826 = 9999
Pr. 826    9999
Pr. 832 = 9999
Pr. 832   9999
Pr. 836 = 9999
Pr. 836    9999
Pr. 836
Pr. 832
Pr. 826
Pr. 74
Pr. 822
Pr. 74
Speed command
Torque command