Mitsubishi Electronics FR-A700 Manual De Usuario

Descargar
Página de 523
25
Control circuit specifications
2.3 Control circuit specifications
2.3.1
Control circuit terminals
 indicates that terminal functions can be selected using Pr. 178 to Pr. 196 (I/O terminal function selection) (Refer to page 231.)
(1) Input signals
Ty
p
e Terminal
Symbol
Terminal 
Name
Description
Rated 
Specifications
Refer to 
page
C
o
nt
ac
t i
npu
t
STF
Forward 
rotation start
Turn ON the STF signal to start forward 
rotation and turn it OFF to stop.
When the STF and 
STR signals are 
turned ON 
simultaneously, the 
stop command is 
given. 
Input resistance 
4.7k
Ω
Voltage at 
opening: 21 to 
27VDC
Contacts at 
short-circuited: 4 
to 6mADC
STR
Reverse 
rotation start
Turn ON the STR signal to start reverse 
rotation and turn it OFF to stop.
STOP
Start self-
holding 
selection
Turn ON the STOP signal to self-hold the start signal.
RH, 
RM, RL
Multi-speed 
selection
Multi-speed can be selected according to the combination of RH, 
RM and RL signals.
JOG
Jog mode 
selection
Turn ON the JOG signal to select Jog operation (initial setting) 
and turn ON the start signal (STF or STR) to start Jog operation.
Pulse train 
input
JOG terminal can be used as pulse train input terminal. To use as 
pulse train input terminal, the Pr. 291 setting needs to be changed.
(maximum input pulse: 100kpulses/s)
Input resistance 
2k
Ω
Contacts at 
short-circuited: 8 
to 13mADC
RT
Second 
function 
selection
Turn ON the RT signal to select second function.
When the second function such as "second torque boost" and 
"second V/F (base frequency)" are set, turning ON the RT signal 
selects these functions.
Input resistance 
4.7k
Ω
Voltage at 
opening: 21 to 
27VDC
Contacts at 
short-circuited: 4 
to 6mADC
MRS
Output stop
Turn ON the MRS signal (20ms or more) to stop the inverter 
output.
Use to shut off the inverter output when stopping the motor by 
electromagnetic brake.
RES
Reset
Use to reset fault output provided when fault occurs.
Turn ON the RES signal for more than 0.1s, then turn it OFF.
In the initial status, reset is set always-enabledBy setting Pr. 75
reset can be set enabled only at fault occurrence. Recover about 
1s after reset is cancelled.
AU
Terminal 4 input 
selection
Terminal 4 is valid only when the AU signal is turned ON. (The 
frequency setting signal can be set between 4 and 20mADC.)
Turning the AU signal ON makes terminal 2 (voltage input) 
invalid.
PTC input
AU terminal is used as PTC input terminal (thermal protection of 
the motor). When using it as PTC input terminal, set the AU/PTC 
switch to PTC.
CS
Selection of 
automatic 
restart after 
instantaneous 
power failure
When the CS signal is left ON, the inverter restarts automatically 
at power restoration. Note that restart setting is necessary for this 
operation. In the initial setting, a restart is disabled.
(Refer to Pr. 57 Restart coasting time in page 266)
SD
Contact input 
common 
(sink)
(initial setting)
Common terminal for contact input terminal (sink logic) and 
terminal FM.
--------------------
External 
transistor 
common 
(source)
Connect this terminal to the power supply common terminal of a 
transistor output (open collector output) device, such as a 
programmable controller, in the source logic to avoid malfunction 
by undesirable currents.
24VDC power 
supply 
common
Common output terminal for 24VDC 0.1A power supply (PC 
terminal).
Isolated from terminals 5 and SE.