Circuit Breaker and Fuse Sizes
The inverter’s connections to input power must include UL Listed inverse time circuit 
breakers with 600V rating, or UL Listed fuses as shown in the table below.
Motor Overload Protection
Hitachi L200 inverters provide solid state motor overload protection, which depends on 
the proper setting of the following parameters:
• B012 “electronic overload protection”
• B212 “electronic overload protection, 2nd motor”
Set the rated current [Amperes] of the motor(s) with the above parameters. The setting 
range is 0.2 * rated current to 1.2 * rated current.
WARNING: When two or more motors are connected to the inverter, they cannot be 
protected by the electronic overload protection. Install an external thermal relay on each 
motor.
Input 
Voltage
Motor Output
Inverter Model
Fuse (A)
(UL-rated, 
class J, 600V)
kW
HP
200V
0.2 1/4
L200-002NFEF/NFU
10
0.4
1/2
L200-004NFEF/NFU
10
0.55
3/4
L200-005NFEF
10
0.75
1
L200-007NFEF/NFU
15
1.1
1 1/2
L200-011NFEF
15
1.5
2
L200-015NFEF/NFU
20 (single ph.)
15 (three ph.)
2.2
3
L200-022NFEF/NFU
30 (single ph.)
20 (three ph.)
3.7
5
L200-037LFU
30
5.5
7 1/2
L200-055LFU
40
7.5
10
L200-075LFU
50
400V
0.4
1/2
L200-004HFEF/HFU
3
0.75
1
L200-007HFEF/HFU
6
1.5
2
L200-015HFEF/HFU
10
2.2
3
L200-022HFEF/HFU
10
3.0
4
L200-030HFEF
15
4.0
5
L200-040HFEF/HFU
15
5.5
7 1/2
L200-055HFEF/HFU
20
7.5
10
L200-075HFEF/HFU
25