Schneider Electric HRB1684301-01 Manual De Usuario

Descargar
Página de 148
HRB1684301-01
141
Chapter 17
MID compliance
This section applies only to the PM5561 (referred to in the section as the meter) and 
contains descriptions and procedures that supplement the meter installation sheet. The 
information contained here supports the meter’s declaration of compliance with the 
Measuring Instruments Directive (2004/22/EC).
MID overview
Directive 2004/22/EC is the Measuring Instruments Directive (“MID”) from the 
European Parliament & Council that harmonises many aspects of legal metrology 
across the EU states.
Scope
Although MID applies to various measuring instruments, the scope of this section is 
limited only to the MID standards that apply to AC electricity metering equipment:
EN 50470-1:2006
Electricity metering equipment (a.c.) 
 Part 1: General requirements, tests and test 
conditions - Metering equipment (class indexes A, B and C)
EN 50470-3:2006
Electricity metering equipment (a.c.) 
 Part 3: Particular requirements - Static 
meters for active energy (class indexes A, B and C)
Related topics
Search the internet for “Measuring Instruments Directive” or “Directive 2004/22/EC” 
for more information.
MID compliance for the meter
The meter complies to these MID standards and class indexes:
EN 50470-1:2006 Class C
EN 50470-3:2006 Class C
The meter achieves MID compliance through application of Annex B (Type 
Examination) and Annex D (Declaration of Conformity to Type Based on Quality 
Assurance of the Production Process).
Specifications relevant to MID
The meter meets all specifications listed in “Specifications” on page 27. See that 
section for mechanical and electrical specifications such as IP rating, rated operating 
conditions, protective class and environmental conditions.
In addition, the following specifications, function limitations and specific conditions 
relevant to MID:
Applicable MID standards and class index
EN 50470-1:2006 Class C
EN 50470-3:2006 Class C
Type of measuring equipment
Static watt-hour meter
Intended use
Indoor use only, permanently mounted in residential, 
commercial or light industrial applications, where levels of 