PowerLogic™ PM5500 series user manual 
Chapter 2—Hardware reference
HRB1684301-01
23
Balanced 3-phase Wye system with 2 CTs
The current for the unconnected current input is calculated so that the vector sum for all 
three phase currents equal zero.
Balanced 3-phase Wye or Delta system with 1 CT
The currents for the unconnected current inputs are calculated so that their magnitude 
and phase angle are identical and equally distributed, and the vector sum for all three 
phase currents equal zero.
NOTE: You must always use 3 CTs for 3-phase 4-wire center-tapped Delta or 
center-tapped open Delta systems.
Neutral and ground current
The fourth current input (I4) can be used to measure current flow (In) in the neutral 
conductor, which can then be used to calculate residual current. The meter refers to 
residual current as ground current (Ig).
For 4-wire Wye systems, ground current is calculated as the difference between the 
measured neutral current and the vector sum of all measured phase currents.
Control power wiring
For wiring instructions and safety precautions, see the meter installation sheet that was 
shipped with your meter, or download a copy at www.schneider-electric.com.
The meter can be powered from an AC or DC power source.
L1 and L2 are non-polarized. If using an AC power supply with neutral, connect 
neutral to the meter’s L2 terminal.
Always use a fuse on L1. Fuse L2 when connecting an ungrounded neutral to the 
control power.
If using a control power transformer, fuse both primary and secondary sides of the 
transformer.
The fuses / circuit breakers must be rated for the installation voltage and sized for 
the available fault current.
Communications
This section provides additional information about the communications ports and 
topologies supported by the meter. You must wire and configure the RS-485 port and/or 
the Ethernet port in order to communicate with the meter.
Serial communications
The meter supports serial communications through the RS-485 port. Up to 32 devices 
can be connected on a single RS-485 bus.
In an RS-485 network, there is one master device, typically an Ethernet to RS-485 
gateway. It provides the means for RS-485 communications with multiple slave devices 
(for example, meters). For applications that require only one dedicated computer to 
communicate with the slave devices, an RS-232 to RS-485 converter can be used as 
the master device.