Chapter 10—Alarms
PowerLogic™ PM5500 series user manual
Digital alarms
Digital alarms monitor the ON or OFF state of the meter’s digital inputs (S1 to S4).
Digital alarm with setpoint delay
To prevent false triggers from erratic signals, you can set up a time delay for the digital 
alarm.
NOTE: To prevent filling the alarm log with nuisance alarm trips, the digital alarm is 
automatically disabled if the digital input changes state more than 4 times in one 
second or more than 10 times in ten seconds. See “Digital input setup” on page 72 to 
adjust the Debounce setting for the digital inputs.
Standard alarms
Standard (1-Sec) alarms have a detection rate equal to the 50/60 meter cycle, which is 
nominally 1 second if the meter’s frequency setting is configured to match the system 
frequency (50 or 60 Hz). These setpoint-driven alarms monitor certain behaviors, 
events or unwanted conditions in your electrical system.
Many of the standard alarms are three-phase alarms. Alarm setpoints are evaluated for 
each of the three phases individually, but the alarm is reported as a single alarm. The 
alarm pickup occurs when the first phase exceeds the alarm pickup magnitude for the 
pickup time delay. The alarm is active as long as any phase remains in an alarm state. 
The alarm dropout occurs when the last phase drops below the dropout magnitude for 
the dropout time delay. 
Digital alarms 
Alarm label
Description
Digital Alarm S1
Digital input 1
Digital Alarm S2
Digital input 2
Digital Alarm S3
Digital input 3
Digital Alarm S4
Digital input 4
Adding setpoint delays to a digital alarm
A
Pickup setpoint (1 = ON)
∆T2
Dropout time delay (in seconds)
B
Dropout setpoint (0 = OFF)
EV2
End of alarm condition
∆T1
Pickup time delay (in seconds)
∆T3
Alarm duration (in seconds)
EV1
Start of alarm condition
EV1
EV2
0
1
ΔT1
ΔT
2
ΔT3
Standard (1-Sec) alarms 
Alarm label
Valid range and resolution
1
Units
ION Setup
Meter display
ION Setup
Meter display
Over Phase Current
Over Current, Ph
0.000 to 99999.000
0 to 99999
A
Under Phase Current
Under Current, Ph
0.000 to 99999.000
0 to 99999
A
Over Neutral Current
Over Current, N
0.000 to 99999.000
0 to 99999
A