Schneider Electric PM5300 Manual De Usuario

Descargar
Página de 120
100
© 2014 Schneider Electric All Rights Reserved
Chapter 13—Meter resets
PowerLogic™  PM5300 series user guide
5. Press Yes to confirm the reset or No to cancel and return to the previous screen.
Single resets
Single resets allow you to clear data only in a specific register or register type.
1. Navigate to Maint > Reset.
2. Move the cursor to point to Single Reset, then press Select.
3. Move the cursor to point to the parameter you want to reset, then press Reset. If 
there are additional options for the parameter, press Select, move the cursor to 
point to the option you want, then press Reset.
4. Enter the reset password if prompted (default is “0000”), then press OK.
5. Press Yes to confirm the reset or No to cancel and return to the previous screen.
Single reset options
Parameter
Option
Description
Energy
Accumulated
Clears all accumulated energy values (kWh, 
kVARh, kVAh).
Demand
Power, Current
Select which demand registers to clear 
(power demand, current demand or input 
metering demand).
Alarms
Event Queue
Clears the alarm event queue register.
History Log
Clears the alarm history log.
Counters
All Alarm Counts, 
(various alarm 
counters) — see the 
next table
Select “Counters”, then select which counter 
to clear (choose all or individual alarm 
counters listed in the “Alarm counter options”  
table below).
Status Inputs
Timers
All Dig In Timers, 
Status Input S1, 
Status Input S2
Select “Timers”, then select which status 
input timer to clear (choose all or individual 
status input timers).
Counters
All Dig In Counters, 
Status Input S1, 
Status Input S2
Select “Timers”, then select which status 
input counter to clear (choose all or individual 
status input counters).
Digital Outputs
Timers
All Dig Out Timers, 
Digital Output D1, 
Digital Output D2, 
Relay R1, 
Relay R2
Select “Timers”, then select which digital 
output timer to clear (choose all or individual 
digital output timers).
Counters
All Dig Out Counters, 
Digital Output D1, 
Digital Output D2, 
Relay R1, 
Relay R2
Select “Timers”, then select which digital 
output counter to clear (choose all or 
individual digital output counters).
Active Load Timer
Clears and restarts the load operation timer.
Multi-Tariff
Clears accumulated values in all tariff 
register.
Alarm counter options
Alarm counter
Option
Description
Current
Over Current, Ph
Select which alarm counter register to reset from 
the current alarm condition counters.
Under Current, Ph
Over Current, N
Over Current, Gnd
Voltage
Over Voltage, L-L
Select which alarm counter register to reset from 
the voltage alarm condition counters.
Under Voltage, L-L
Over Voltage, L-N
Under Voltage, L-N
Over Voltage Unbal
Over Voltage THD
Phase Loss