PowerLogic™  PM5300 series user guide 
Chapter 14—Maintenance and Upgrades
© 2014 Schneider Electric All Rights Reserved
106
The power meter does not contain any user-serviceable parts. If the power meter requires 
service, contact your local sales representative. Do not open the power meter. Opening 
the power meter voids the warranty.
Getting Technical Support
Please refer to the Technical Support Contacts provided in the power meter shipping 
carton for a list of support phone numbers by country, or go to 
www.schneider-electric.com
, then navigate to Support area for contact information.
Register List
To download the latest version of the power meter PM5300 Modbus register list, go to 
www.schneider-electric.com. 
Type PM5300 in the search field. 
Table 14–1: Troubleshooting
Potential Problem
Possible Cause
Possible Solution
The maintenance (wrench) 
icon is illuminated on the 
power meter display.
When the maintenance (wrench) icon 
is illuminated, it indicates an event 
has occurred which may require 
attention.
Go to [Maint] > [Diag]. Event messages 
display to indicate the reason the icon is 
illuminated. Note these event messages and 
call the Technical Support or contact your 
local sales representative for assistance.
The display is blank after 
applying control power to 
the power meter.
The power meter may not be 
receiving the necessary power.
The display may have timed out.
Verify that the power meter line and terminals 
are receiving the necessary power. 
Verify that the heartbeat LED is blinking.
Press a button to see if the display timed out.
The data being displayed is 
inaccurate or not what you 
expect.
Incorrect setup values.
Check that the correct values have been 
entered for power meter setup parameters 
(CT and VT ratings, Nominal Frequency, and 
so on). See “Configuring the basic setup 
parameters” on page 34
 for setup 
instructions.
Incorrect voltage inputs.
Check power meter voltage input terminals (1, 
2, 3, 4) to verify that adequate voltage is 
present.
Power meter is wired improperly.
Check that all CTs and VTs are connected 
correctly (proper polarity is observed) and that 
they are energized. Check shorting terminals. 
See the recommended torque in the Wiring 
section of the installation manual.
Cannot communicate with 
power meter from a remote 
personal computer.
Power meter address is incorrect.
Check to see that the power meter is correctly 
addressed. See “Communications setup” on 
page 36
 for instructions.
Power meter baud rate is incorrect.
Verify that the baud rate of the power meter 
matches the baud rate of all other devices on 
its communications link. See 
“Communications setup” on page 36 fo
instructions.
Communications lines are improperly 
connected.
Verify the power meter communications 
connections. Refer to the “Communications” 
on page 26 
section for instructions.
Communications lines are improperly 
terminated.
Check to see that a multi-point 
communications terminator is properly 
installed. 
Incorrect route statement to power 
meter.
Check the route statement. Contact Global 
Technical Support for assistance.
Energy/Alarm LED not 
working.
May have been disabled by user.