Schneider Electric PM5300 Manual De Usuario
PowerLogic™ PM5300 series user guide
Chapter 7—Alarms
© 2014 Schneider Electric All Rights Reserved
69
Setting Up Unary Alarms
To set up unary alarms:
1. Press Unary. The unary alarm
Select screen appears.
2. Press
▼
and
▲
to scroll
through the list of unary alarms.
3. Press Edit to select an alarm to
be configured.
4. Press Edit to select Enable.
5. Press + and - to scroll between
Yes and No.
6. Press OK to enable or disable
the alarm.
7. Press
▼
to select Priority.
8. Press + and - to scroll through
priority options Low, None,
High, or Medium.
High, or Medium.
NOTE:
on page 66 for more
information.
information.
9. Press OK to set the priority.
10. Press
▼
to select Select
Digital Output, then press Edit.
NOTE:
The digital output
behavior mode must be Timed
or Coil Hold to turn on when a
unary alarm event occurs.
or Coil Hold to turn on when a
unary alarm event occurs.
11. Press + and - to scroll through
the list of digital outputs to
associate with the alarm.
associate with the alarm.
12. Press OK to select a digital
output to be associated with the
selected alarm.
selected alarm.
13. If the selected digital output
already has an association that
will be lost by making the new
selection, a confirmation
screen appears.
— Press Yes to accept the
will be lost by making the new
selection, a confirmation
screen appears.
— Press Yes to accept the
changes and return to the
previous screen.
previous screen.
— Press No to keep the
existing configuration in use
and return to the previous
screen.
and return to the previous
screen.
14. Press
▲
to save all alarms
selections and return to the
previous screen.
previous screen.
15. Press
▲
to save all unary
alarm selections.