Setting Up Unary Alarms 
To set up unary alarms:
1. Press Unary. The unary alarm 
Select screen appears.
2. Press 
▼ 
and 
 to scroll 
through the list of unary alarms.
3. Press Edit to select an alarm to 
be configured.
4. Press Edit to select Enable.
5. Press and to scroll between 
Yes and No.
6. Press OK to enable or disable 
the alarm.
7. Press 
 to select Priority.
8. Press and - to scroll through 
priority options Low, None, 
High, or Medium.
NOTE:
on page 66 for more 
information.
9. Press OK to set the priority.
10. Press 
 to select Select 
Digital Output, then press Edit.
NOTE:
The digital output 
behavior mode must be Timed 
or Coil Hold to turn on when a 
unary alarm event occurs.
11. Press and - to scroll through 
the list of digital outputs to 
associate with the alarm.
12. Press OK to select a digital 
output to be associated with the 
selected alarm.
13. If the selected digital output 
already has an association that 
will be lost by making the new 
selection, a confirmation 
screen appears. 
— Press Yes to accept the 
changes and return to the 
previous screen.
— Press No to keep the 
existing configuration in use 
and return to the previous 
screen.
14. Press 
 to save all alarms 
selections and return to the 
previous screen.
15. Press 
 to save all unary 
alarm selections.