Schneider Electric PM5300 Manual De Usuario
PowerLogic™ PM5300 series user guide
Chapter 8—Data Logs
© 2014 Schneider Electric All Rights Reserved
75
Chapter 8—Data Logs
This chapter briefly describes the following logs of the power and energy meter:
•
Alarm Log
•
User-defined data log
Logs are files stored in the non-volatile memory of the power and energy meter and are
referred to as “on-board logs”.
referred to as “on-board logs”.
Data Logs
The PM5300 series records and stores readings at regularly scheduled intervals in one
independent data log. This log will be in disabled state from the factory. You can set up
the data log to store the following information.
independent data log. This log will be in disabled state from the factory. You can set up
the data log to store the following information.
•
Time Interval: 15, 30, 60 minutes
•
First-in-first-out (FIFO) or Fill and Hold
•
Values logged - up to 2 registers along with data and time of each log entry
The registers list for configuring the data logs
Description
Number of Registers
Data Type
Register Number
Active energy delivered
4
Integer
3204
Active energy received
4
Integer
3208
Reactive energy delivered
4
Integer
3220
Reactive energy received
4
Integer
3224
Apparent energy delivered
4
Integer
3236
Apparent energy received
4
Integer
3240
Status input 1 counter
1
Integer
8915
Status input 2 counter
1
Integer
8919