Features 
 The 
 control panel is shown in
Fig. 1.
PROCESSOR MODULE 
 This module contains the
operating software and controls  the  operation of the
machine. It continuously monitors information received
from the various temperature thermistors and communi-
cates with the relay  module  to increase or decrease  the
active stages of capacity. The processor module also
controls the EXV driver module, commanding it to open
or close each electronic expansion valve in order to main-
tain approximately 20 F of superheat 
  t h e
cylinders of each of the 
 compressors, Information is
transmitted between the processor module and the relay
module,  EXV  driver 
  a n d   k e y b u a r d   d i s p l a y
module through a 3-wire communications bus.
8
9
EXV  (ELECTRONIC EXPANSION 
 DRIVER
MODULE  -- The  EXV  driver module operates  the elec-
tronic expansion valves (based on commands from the
processor) and monitors the status of the 
 pressure
switches and the refrigerant Ioss of charge switches.
If the loss of charge switch opens due 
to 
a low refrig-
erant charge, the EXV driver module detects a zero
voltage condition in the loss of charge switch electrical
circuit and communicates this information to the pro-
cessor module. The processor module immediately shuts
down all compressors in the affected refrigeration circuit.
During operation,  if the  EXV  driver  module detects
zero voltage in the  oil  pressure switch electrical circuit
for 45 consecutive seconds (due to an open oil pressure
switch), it communicates this information to the pro-
cessor module. The processor module 
down 
 compressors in the affected refrigeration 
At start-up, if the oil pressure switch has not closed by the
end of a 
 time period the EXV driver module
senses this and the processor module immediately shuts
down all compressors in the affected refrigeration circuit.
If a shutdown occurs due to loss of 
 or low oil
pressure,  the EXV 
 module communicates this to
the processor module and the processor module locks the
compressors off in the affected refrigeration circuit.
The proper fault code(s) will appear on the display
whenever a safety switch opens.
KEYBOARD AND DISPLAY 
 
 (Fig. 2)
This device consists of a keyboard with   function keys,
5 operative keys, 12 numeric keys (0 to       and an
alphanumeric g-character LCD. Key 
 
 explained
in Table 
Table 1 
 Keyboard and Display 
 
Key Usage
FUNCTION
K E Y S
 
 
 Module
 
 Control Power ON Light
 RUN/STANDBY Switch
 
 Discharge Pressure Gage 
 Suction 
Pressure Gage Valves
 
 Suction Pressure Gages
 Discharge Pressure Gages
 Compressor ON Lights
 Control Circuit 
Fuses
10
 Alarm Light
OPERATIVE
Fig. 1 
 Control Panel
K E Y S
qCLR
LOW-VOLTAGE RELAY MODULE -- This module
closes contacts to 
 compressors, solenoid valves
and unloaders. It also senses the condition of the com-
pressor safeties and transmits this information to the
processor module.
q
Status 
 
 diagnostic
codes 
and 
 
information about the machine
Quick Test 
 Checking inputs
and outputs for proper
operation
History 
 This key appears on
the keyboard, but is not used on
the 
 
 E machines
Service 
 Entering specific
unit configuration information
Set Point 
 Entering operating
set points and day/time
information
Schedule 
 Entering occupied/
unoccupied 
schedules 
for unit
operation
USE
Expand Display 
 Displaying 
a
non-abbreviated expansion of
the display
Clear 
 Clearing the screen of
all displays
Up Arrow 
 
 
previous display 
Down Arrow 
 Advancing to
next display position
2