When loading products: 
  
- Do not block the lower ventilation grille with the packages about to be loaded.    (Fig. 5)  
- Do not block the return vents that ensure a proper refrigerated air circulation.   (Fig. 6) 
- Do not over hang the shelf. 
- Do not press the product against the rear wall 
- Never exceed the shelf weight limits. (See Shelf Specifications Pg.10) 
    
 
 
FIGURE 5                             FIGURE 6
 
 
UNIT OPERATION AND COMPONENTS 
 
ELECTRONIC TEMPERATURE CONTROL: 
 
 
The unit is provided with an electronic temperature control that controls the operation of the unit based 
on the temperature of the air entering the evaporator at the front of the unit. 
  
In order to achieve the desired product temperature, the electronic control is factory adjusted to turn off 
the refrigeration system at 35ºF and start it at 39.5ºF. 
  
When  you plug the unit  in,  the control display  will  illuminate. However,  there is  a start-up delay  of 2 
minutes  before  the  compressor(s)  are  energized.  This  delay  avoids  the  possibility  that  during  a  power 
failure the compressors are forced to restart before the refrigerant pressures are equalized. 
  
The control has been factory-adjusted with a defrosting cycle scheduled to last 6 minutes every hour to 
ensure that the evaporator performs without any ice build-up. 
  
None of the factory-programmed electronic control parameters can be modified unless an access code is 
entered (only your distributor's technical personnel have that code).