Problem
Possible Cause
Remedy
[1] The unit will not 
start.
a) Power Supply
1. Unplugged, off, 
blown fuse, or tripped 
or defective circuit 
breaker.
1. Turn on, replace, or check 
and reset. Call electrician if 
breaker trips repeatedly.
2. Loose connection.
2. Tighten.
3. Not within 
specifications.
3. Refer to nameplate and 
correct.
b) Cord and Plug
1. Defective.
1. Replace.
c) Control Switch
1. "OFF" position.
1. Move to "ON" position.
2. Bad contacts.
2. Check for continuity and 
replace.
d) Transformer
1. Open coil winding.
1. Check continuity and 
replace.
e) Wiring to Control Board 1. Loose connections or 
open.
1. Check for continuity and 
replace.
f) Control Board
1. In alarm.
1. See "III.A. Alarm Signals."
2. Defective.
2. Replace.
[2] Cabinet, rail, or 
condenser fan will 
not start.
a) Fan Motor
1. Motor winding open.
1. Replace.
2. Bearing worn out.
2 Replace.
3. Wiring to fan motor.
3. Check for loose or open 
connection, and replace.
4. Fan blade bound.
4. Check and replace.
b) Evaporator Fan, Rail 
Fan, or Compressor 
Relay 
1. Bad contacts.
1. Check for continuity and 
replace.
2. Coil winding open.
2. Replace.
c) Control Board
1. Defective.
1. Replace.
[3] Compressor will 
not start or stops 
operating.
a) Compressor Relay
1. Bad contacts.
1. Check for continuity and 
replace.
b) Compressor Control 
Relay
1. Bad contacts.
1. Check for continuity and 
replace.
2. Open winding.
2. Replace.
c) Start Relay
1. Bad contacts.
1. Replace.
2. Coil winding open.
2. Replace.
d) Start Capacitor
1. Defective.
1. Check and replace.
e) Wiring to Compressor
1. Loose connection(s).
1. Tighten.
2. Faulty.
2. Check continuity and 
replace.
7. Control Board Alarms (EA and ED)
"EA" is displayed when an EEPROM write error is detected. "ED" is displayed when an
EEPROM verification or read error is detected.
Reset Options
Replacing the control board with a functioning control board will eliminate this alarm 
condition.
B. Service Chart
1. No Operation