Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL
68-0282—07
4
INSTALLATION
A fresh air duct and damper must be installed between the 
outdoors and the return side of the HVAC equipment. The 
W8150 control will be mounted near the HVAC system and 
wired between the thermostat and the fan control. 
You will need…
• W8150 Fresh Air Ventilation Control.
• damper.
• transformer.
• insulated ductwork.
• outdoor weather hood.
• starting collar.
• access to 120 Vac power.
• airflow measuring tool.
TIPS:
• To meet ASHRAE 62.2-2010, system must have at least a 
MERV 6 filter installed.
• In cold climates, balanced ventilation is recommended. An 
exhaust fan or heat recovery ventilator can be used.
• Humid climates may require additional dehumidification 
equipment.
Choosing a location…
When choosing locations for equipment, duct connections, 
and fresh air intake, be sure to consult local code 
requirements.
16
REMOTE
Remote switch (two 
terminals)
24 Vac powered contacts allow a remote switch closure to call for 
ventilation.
17
AUX
Auxiliary (two terminals)
24 Vac dry contacts allow W8150 to control an auxiliary device, such as 
exhaust fan or HRV/ERV, with a call for ventilation.
18
DAMPER
Damper (two terminals)
24 Vac powered contacts control fresh air damper.
19
XFMR C
24 Vac ventilation control 
common
Supplies power to W8150 and damper from transformer provided.
20
XFMR R
24 Vac ventilation control 
power
Supplies power to W8150 and damper from transformer provided.
 No.
Name
Description
Function
Device 
Number
Component Location
1
Fresh air intake Install away from known sources 
of pollutants such as auto 
exhaust, dryer vent exhaust or 
chimney smoke.
2
Fresh air duct
Install between weather hood and 
upstream of equipment filter and 
downstream of any duct-mounted 
sensor.
3
Damper
Install damper in fresh air duct, 
where convenient. Optionally, 
install heat recovery ventilator.
4
Control
Locate the control for convenient 
access and for easy wire routing.
5
Transformer
Locate where convenient for line 
voltage connection.
Filter
Locate filter downstream of fresh 
air intake.
M19993
1
2
1
3
TYPICAL ATTIC
INSTALLATION
TYPICAL BASEMENT
INSTALLATION
TYPICAL HRV/ERV
INSTALLATION
3
2
HRV/ERV
6
6
6
4
4
5
1
3
2
Ventilation Control
Ventilation Contro l
Auto
Continuous
 (Remote Only)             
4