APPLICATION
Model FSD-331 is a high performance combination fire smoke damper 
with extremely low leakage. High strength airfoil blades ensure the 
lowest resistance to airflow in HVAC systems with velocities to 2000 
fpm (10.2 m/s) and pressures to 4 in. wg (1 kPa). Model FSD-331 may 
be installed vertically (with blades running horizontal) and is rated for 
airflow and leakage in either direction.
RATINgs
UL 555 Fire Resistance Rating 
 
Fire Rating: 
3
 
hours 
 
Dynamic Closure Rating: Actual ratings are size dependent 
 
Max. Velocity: 
up to 2000 fpm (10.2 m/s) 
 
Max. Pressure: 
4 in. wg (1 kPa)
UL555S Leakage Rating 
 
Leakage Class: 
 
Operational Rating: 
Actual ratings are size dependent 
 
Max. Velocity: 
up to 3000 fpm (15.2m/s) 
 
Max. Pressure: 
4 in. wg (1 kPa) 
 
Maximum Temperature:  350°F (177°C)- depending upon the 
 
 
actuator
sTANdARd CONsTRuCTION
 
Frame:  
5 in. x 1 in. (127mm x 25 mm) 
 
 
galvanized steel hat channel with 
 
 
reinforced corners. A low profile head 
 
 
and sill are used on sizes less than 
 
 
17 in. (432mm) 
 
Blades:  
Double skin airfoil shape of 
 
 
galvanized steel with full length 
 
 
structural reinforcement. 14 ga. 
 
 
(2 mm) equivalent thickness. 
 
Seals: 
Extruded silicone rubber blade seals 
 
 
Flexible stainless steel jamb seals. 
 
Linkage: 
Concealed in jamb. 
 
Closure Device: 
RRL 165°F (74°C) 
 
Axles: 
1
2
 in. (13mm) dia. plated steel. 
 
Bearings: 
Bronze sleeve type.
sIze LImITATIONs:
 
minimum size: 
8 in. W x 6 in. H 
 
 
(203 mm W x 152mm H) 
 
maximum size (Vertical Only):  
 
Single Section: 
32 in. W x 36 in.H 
 
 
(813mm W x 914mm H) or  
 
 
30 in. W x 48 in. H 
 
 
(762mm x 1219mm) 
 
Multiple Section:
 
120 in. W x 96 in. H 
 
 
(3048mm W x 2438mm H)
OPTIONAL FeATuRes:
• RRL/OCI (Open closed indication switches)
•  165ºF (74°C), 212ºF (100°C), 250ºF (121°C), 350ºF (177°C) RRL's 
available
•  TOR (remote override closure allows damper to perform smoke 
management functions during a fire emergency.)
•  Electric or pneumatic actuators to accomplish smoke management 
and system functions.
• POC retaining angles
• Smoke detectors
• Momentary Switch
• Transitions (R, C, O)
• PRV (pneumatic relief valve)
• Security Bars
• Sealed transitions and sleeves
model Fsd-331
Combination Fire smoke dampers
 
Steel Airfoil Blades
UL 555S Leakage Class I
UL555 3 Hour Fire Resistance Rating
*W&H dimensions furnished approximately 
1
/
in. ( 6 mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
H*
W*
LH
RH
Model FSD-331 meets the requirements for fire 
dampers, smoke dampers and combination fire 
smoke dampers established by:
National Fire Protection Association 
    NFPA Standards 80, 90A, 92A, 92B, 101 & 105
IBC  International Building Codes
ICBO  uniform Building Codes 
CsFm California state Fire marshal
  Fire Damper Listing (#3225-0981:103)
  Leakage (Smoke) Damper Listing (#3230-0981:104)
New York City (MEA listing #260-91-M)
“uL CLAssIFIed (see complete marking on 
product)”
“uL CLAssIFIed to Canadian safety standards 
(see complete marking on product)”
 
Standard 555 & 555S (Listing #R13317) 
Installation instructions available at www.greenheck.com
R
Greenheck Fan Corporation certifies that the 
model FSD-331 shown herein is licensed to 
bear the AMCA Seal. The ratings shown are 
based on tests and procedures performed 
in accordance with AMCA Publication 511 
and comply with the requirements of the 
AMCA Certified Ratings Programs. The 
AMCA Certified Ratings Seal applies to air 