9. ADJUSTMENT OF WATER REGULATING VALVE - WATER-COOLED
MODEL ONLY
The Water Regulating Valve (also called “WATER REGULATOR”) is factory-adjusted.
No adjustment is required under normal use. Adjust the Water Regulator, if necessary,
using the following procedures.
No adjustment is required under normal use. Adjust the Water Regulator, if necessary,
using the following procedures.
1) Attach a pressure gauge to the high-side line of the system. Or prepare a
thermometer to check for the condenser drain temperature.
thermometer to check for the condenser drain temperature.
2) Rotate the adjustment screw by using a flat blade screwdriver, so that the pressure
gauge shows the temperature specified in the table, 5 minutes after a freeze cycle
or icemaking process starts. When the pressure exceeds 235 PSIG, or the
condenser drain temperature exceeds the temperature range, rotate the adjustment
screw clockwise. See Fig. 1.
gauge shows the temperature specified in the table, 5 minutes after a freeze cycle
or icemaking process starts. When the pressure exceeds 235 PSIG, or the
condenser drain temperature exceeds the temperature range, rotate the adjustment
screw clockwise. See Fig. 1.
3) Check that the pressure or the condenser drain temperature holds a stable setting.
MODEL
KML-200MWE
WATER TEMP. (°F)
50
70
90
AMBIENT TEMP. (°F)
70
100
100
105
80
99
105
105
90
99
105
105
100
100
105
105
Fig. 1
CW - Lower
CCW - Higher
CCW - Higher