U-Line CLR2060SSHR Manual De Usuario

Descargar
Página de 118
TROUBLESHOOTING
1.  Unit does not operate (with drain pump; light
on control board is not illuminated)
Cause
a. No electrical power to the unit.
b. Rocker switch set incorrectly.
c. Drain tube is kinked or obstructed.
d. Bad pump. Diagnose by bypassing the pump. 
Pull both pink wires from control board and 
jump the two terminals together. If unit starts 
up, then the pump is bad.
2. Unit does not operate (without drain pump;
light on control board is not illuminated)
Cause
a. No power to unit.
3. Unit does not operate and light on control
board is illuminated
Cause
a. Bad bin thermostat.
b. Bin thermostat set incorrectly.
4. No ice production
Cause
a. No water supplied to unit.
b. Stand pipe not inserted in water trough.
c. Re-circulating pump is defective.
5. Low ice production
Cause
a. High ambient temperatures around unit.
b. Deposit build-up on evaporator grid.
c. Ice thickness dial set incorrectly.
d. Dirty condenser coil.
Remedy
a. Make sure unit is plugged in and outlet
has power.
b. Check switch wiring. Set to “ICE.”
c. Clear the tubing. If water cannot drain from 
pump, unit will shut down due to safety 
design of pump.
d. Change pump. Jumping the two terminals 
together on the control board with a jumper 
wire will eliminate pump from the circuit.
Remedy
a. Jumper plug off power cord.
Remedy
a. Replace bin thermostat. The unit is falsely 
sensing a full bin.
b. Set bin thermostat at the 10:00 position.
Remedy
a. Check that water is connected and turned on.
b. Insert stand pipe securely into water trough.
c. Replace re-circulating pump.
Remedy
a. Lower ice rate is normal with high ambient 
temperatures.
b. Run the unit through a clean cycle. Use only 
U-Line Ice Machine Cleaner.
c. Adjust ice thickness dial accordingly.
d. Clean condenser coil.
105
Design 
Features 
Performance 
CLR2060 MODEL
DO NOT service the unit until the main electrical power has been disconnected.
!
DANGER
!