BEA 10MATRIX Manual De Usuario

Descargar
Página de 12
Page 4 of 5 
 
  
 
 
 
75.1046.04   EN  20080505
8   Adjustments
7   Programming (cont’d)
      IV.  DIPSWITCHES
 
 
A.  After each dipswitch change the sensor launches a learning process.
DIPSWITCH
LEARNING PROCESS
#1
Frequency Adjustments of Loop A  (see ADJUSTMENTS)
#2
Frequency Adjustments of Loop A (with single loop) or Loop B (with Dual Loops)
#3
Relay configuration: Active (Fail-Secure) or Passive (Fail-Safe)(See Programming Step III.)
#4
Automatic Sensitivity Boost (ASB option)  [recommended for improved truck detection] :
During a detection, the sensitivity increases automatically to 8 times the preset sensitivity given by the sensitivity 
potentiometer adjustment. It is limited to the maximum sensitivity (   f = 0.005%). It goes back to the preset value after 
detection stops.
#5
Relay A Function:  Presence or Pulse  (not used with dual loop in combined mode)
#6
Relay A Pulse type:  Entry or Exit  (used only at pulse function)
or Relay B Mode (with dual loop in combined mode) (see drawing on next page)
• Non-Directional:  Relay B provides a pulse according to the dip switches #7 and #8 setting.
• Directional A    B:  Relay B provides a pulse only if loop A is detecting before loop B.  The logic detection takes place
  according to dip switches #7 and #8.
WARNING:  DURING THE DETECTION, THE 2 LOOPS HAVE TO DETECT SIMULTANEOUSLY FOR A SHORT 
PERIOD TO BE ABLE TO DETERMINE THE MOVEMENT DIRECTION.  DURING LOOP INSTALLATION 
MAKE SURE THE 2 LOOPS ARE CLOSE ENOUGH TO EACH OTHER TO ENSURE A COMMON 
DETECTION (TYPICAL 3 FEET).
#7
Relay B Function:  Presence or Pulse  - or - 
Loop Selection for Relay B Pulse:  Pulse on Loop B or Pulse on Loop A (used with dual loop in combined mode)
#8
Relay B Pulse Type:  Entry or Exit  (used only at pulse function)
#9
Pulse Duration for Both Relays (used only at pulse function):  100 ms or 500 ms
#10
Dual Loop Mode:  Independent or Combined A    B  (not used with single loop)
Δ
entry B
Pulse on exit A
Pulse on exit B
 Dual Loop Configuration A
Relay B
(Directional A-> B mode)
Pulse on entry A
Pulse on entry
     
Relay B
(Non-Directional)
Loop A
Loop B
Relay A
Pulse on entry A
Pulse on
B
Pulse on exit A
Pulse on exit B
Loop A
Loop B
Dual Loop Configuration B
Loop A
Loop B
Relay A
Pulse on entry B
Pulse on exit B
Pulse on entry A
Pulse on exit A
Relay B
(Non-Directional)
Pulse on entry B
Pulse on exit B
Pulse on entry A
Pulse on exit A
Relay B
(Directional A-> B mode)
Loop A Loop B
FREQUECY ADJUSTMENT FOR LOOP A FOR SINGLE LOOP DETECTOR
LOOP FREQUENCY
DIPSWITCH #1
DIPSWITCH #2
HIGH
Off
Off
MID HIGH (High - 20%)
On
Off
MID LOW (High - 25%)
Off
On
LOW (High - 30%) 
On
On