3.4  UPS PARALLELED ON THE SAME BATTERY 
 
 
NOTE ! 
A parallel system with a Common Battery for two or more UPS, requires a particular 
installation and adequate setting of some parameters, (accessible only through 
password), and can therefore only be done by a qualified GE engineer. 
 
Usually each UPS Unit runs with its own Battery
In case of parallel units running with a Common Battery (max. 4 UPS - see Fig. 3.4-1), the sharing circuit 
between the individual UPS is integrated in the communication bus of the system in order to assure an 
equal sharing of the Rectifiers output currents. 
 
 
Fig. 3.4-1   Diagram RPA system with UPS on common battery 
1 – 
 
2 – 
 
3 – 
 
4 – 
 
5 – 
 
6 – 
 
7 – 
 
8 – 
Rectifier 
 
Inverter 
 
Automatic Bypass 
 
Manual Bypass 
 
Mains Power 
 
Load Bus Bar 
 
External Battery Fuse 
 
Battery 
 
 
Pay attention to the following recommendations: 
• 
The units delivered for this functioning mode needs a special parameters setting, so they must be 
prepared in advance before the installation. 
• 
The installation must be performed only with the UPS system completely shut down. 
• 
The AC Rectifiers input power (5) must be the same, with clockwise phase rotation for each unit. 
• 
Each Rectifier must be set for the same floating DC voltage and the same Battery current limitation. 
• 
It is mandatory to install the fuses / MCB (7) on each line connecting the Rectifiers to the common 
Battery for maintenance / safety reasons (see Section 4.7.2). 
• 
In case a unit must be powered down for maintenance, switch-OFF the concerned unit before open 
the DC fuses / MCB on the Battery line (7). 
• 
If an emergency generator set supplies the UPS, and the free contact “Generator ON” is connected 
to the Customer Interface, connect a separate NO free contact on each parallel unit. 
• 
Do not connect the temperature sensor for automatic battery floating voltage compensation. 
• 
Do not enable the function Boost charge