6.3.1 User 
parameters 
screen 
 
This screen allows the user to modify some parameters permitting to adapt some functions of the UPS 
to his/her needs, described as follows. 
 
This screen can be accessed by entering MENU/PARAMETER MENU/LEVEL 1: USER and confirming with 
the key Enter
 
PARAMETER MENU 
 
LEVEL 1: USER 
LEVEL 2: SERVICE
 
 
In PARAMETER MENU the buttons + / - / Enter perform the following functions: 
+
 
This key allows to scroll forward to the next screen and, once the key Enter has been pressed, 
to move the horizontal selection to the next editable position. 
- 
This key allows to move the selection to the next parameter and, once the key Enter has been 
pressed, to change the value of the selected character by the underscore cursor. 
Enter 
Start the editing for the currently selected parameter. 
 
 
1.  Date and time set-up 
 
DATE AND TIME 
 D 
Date: 01.01.2005 
Hour: 12:15:45
 
 
 
 
1.  Date and time setup. 
2.  = Day 
= Month 
= Year. 
3.  Date set-up:   the set value is thoroughly checked to be a 
correct format “dd.mm.yyyy”. 
4.  Time set-up:  the set value is thoroughly checked to be a 
correct format “hh.mm.ss”. 
The time is specified in 24 hour format. 
 
 
 
2. Modem 
protocol 
set-up 
 
PROTOCOL SETUP 
Modem enabled = N 
Init=BEQV1X3&D0S0=2 
Alarm=N Delay=30s
 
 
 
 
1. Modem 
protocol 
set-up. 
2.  Y: enables     or     N: disables the modem call. 
3.  Init:  this parameter presents the modem initialization string. 
It can be 39 characters long and considers that a blank 
character terminates the string. 
If no blank character is found then all 39 characters are 
used 
4.  Alarm:  Y/N controls the automatic events signaling through modem. 
If this parameter is set to Y (yes) the UPS itself will call the remote location when a new 
event occurs. 
 
Delay:  This parameter controls the delay between the occurrence of a new event and the 
modem dialing. 
It is useful because since the events typically do not occur isolated but in certain 
sequences, you can eliminate the need for multiple dial-outs for such a sequence of 
events.