7.2.2  Complete UPS shutdown (No Load supply) 
 
 
The Load must be disconnected. 
 
Initial status: 
Load supplied from Inverter.
 
 
 
1. Press total off button. 
• 
Load is disconnected from UPS. 
• 
Rectifier is shut down and all output and 
input contactors will be opened. 
• 
LED’s,  Rectifier, Inverter and Load are 
OFF. 
 
 
2.  Open Q1 (Pos. O). 
• 
LED service check lights up. 
 
 
3.  Disconnect the Battery from the UPS 
in case of External Battery
• 
Wait 5 minutes for DC-Link Capacitors 
discharge. 
 
 
4.  Disconnect the Utility
• 
All LED’s are OFF. 
 
 
End of procedure