Emerson MODBUS 485 Manual De Usuario
BACnet Communications - Thermal Management Products
243
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Reheat
Reheater Lockout
MultiState_Value
316
5582_1
RW
1 = disabled
2 = enabled
2, 3, 4,
5, 6
Humidifier
Humidifier Lockout
MultiState_Value
328
5583_1
RW
1 = disabled
2 = enabled
2, 3, 4,
5, 6
Air Economizer
Air Economizer Availability
MultiState_Value
340
5599_1
RD
1 = Not Available
2 = Available
2, 3, 4,
5, 6
Air Economizer Control Source
MultiState_Value
341
5602_1
RW
1 = disabled
2 = internal
3 = external
2, 3, 4,
5, 6
Global Condensers - GC Low Noise Mode
Condenser Low Noise Mode
State
MultiState_Value
374
5546_1_1
RD
1 = Inactive
2 = Active
(Interval)
3 = Active (Full
Day)
3, 4, 5,
6
Condenser Low Noise Mode
Schedule Control
MultiState_Value
375
5547_1_1
RW
1 = disabled
2 = enabled
3, 4, 5,
6
Table 81
Extra Notes to Table 80
Number
Description
1
This point is supported on:
iCOM controller version 1.04.042.STD
2
This point is supported on:
iCOM controller version 2.00.11R for US
iCOM controller version 2.00.12R (for Japan and China – language corrections only)
3
This point is supported on:
iCOM controller version 2.01.23R
4
This point is supported on:
iCOM controller version 2.02.16R
5
This point is supported on:
iCOM controller version 2.03.27.07R
6
This point is supported on:
iCOM controller version 2.01.32.02R
Table 80
Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Multistate Data (continued)
Data Label
Object Type
Instance
Object Name
Access
Notes
Extra
Notes