Configuring the Modbus Models
 
31007492                                                                                                                                                                                                                                    
29
3.4 Modbus Port Parameters
3.4.1
Information You Will Need
You will need the following information for each port that you will use in
your application.  Parameters are explained in the sections indicated.
Port Type (see Section 3.4.2)
Modbus Master
Modbus Slave
Modbus Network
Modbus `Silent Master' Network
Slave Device Address (see Section 3.4.3)
1 ... 247
Communication Parameters (see Section 3.4.4)
Baud Rate:  50 ... 19200
Stop Bits:  1 or 2
Parity Mode:  Even, Odd, or None
Communication Mode:  ASCII or RTU
Note:  Models NW-BM85C002 and NW-BM85D008 do not have a
Stop Bits setting.  These models default to 8 data bits with 1 Stop Bit.
Port Priority (see Section 3.4.5)
1 ... 4
Link Timeout (see Section 3.4.6)
1 ... 3000 multiples of 100 milliseconds
Modem Booster (see Section 3.4.7)
Yes or No
Modbus Plus Address Table (see Section 3.4.8)
A routing table with up to 64 entries for translating Modbus addresses
to Modbus Plus network routing paths.