 Please read this instruction sheet carefully before use and follow this instruction to operate the device in order 
to prevent damages on the device or injuries to staff. 
 
 
Switch off the power before wiring.
 
 
This instruction sheet only provides introductory information on electrical specification, functions, wiring, 
trouble-shooing the peripherals for DVPPF02-H2. Details of PROFIBUS DP protocol are not included in this 
sheet. For more information on PROFIBUS DP protocol, please refer to relevant reference or literatures.
 
 
DVPPF02-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, 
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the 
device (e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device 
may occur. 
 
 
DVPPF02-H2 is to be used for controlling the operating machine and equipment. In order not to damage it, 
only qualified professional staff familiar with the structure and operation of if can install, operate, wire and 
maintain it.
 
 
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. 
Check all the wiring again before switching on the power, and DO NOT touch any terminal when the power is 
switched on. Make sure the ground terminal 
  is correctly grounded in order to prevent electromagnetic 
interference.
 
 Introduction
 
Thank  you for choosing Delta DVPPF02-H2 PROFIBUS DP communication module. DVPPF02-H2 can 
be applied to the connection with DVP-EH2 series PLC MPU in a PROFIBUS DP network. DVPPF02-H2 
does not need to be connected to an external power supply. The power will be supplied from DVP-EH2 
once it is connected to DVP-EH2.   
 Features
 
1.  Supports  loop-type data  exchange between DP  master and  many slaves. 
2.  Supports GSD files in PROFIBUS DP network  configuration  tools. 
3.  Supports 4 slots in PROFIBUS DP network  configuration  tools. 
4.  Auto-detects baud rates; supports Max. 12Mbps. 
5.  The length of I/O data can  be freely  configured through PROFIBUS DP network  configuration  tools. 
Max. input data length = 100 words (the sum of 4 slots); Max. output data length = 100 words (the 
sum of 4 slots). 
6.  Error  code  diagnosis. 
 Product Profile & Outline 
 
82  [3.228]
9
0
  
[3
.5
4
3
]
40  [1.575]
7
  
[0
.2
7
6
]
PO WER
NET
X
1 6
X
1 6
2
3
5
4
6
7
1
8
 
Unit: mm 
 
1 Extension  port 
2 Address setup switch 
3 POWER indicator 
4 NET indicator 
5 PROFIBUS DP connector 
6 Extension  module  interface
 
7 DIN rail clip 
8 DIN rail 
 
ENGLISH 
 Specifications 
PROFIBUS DP Connector 
Interface 
DB9 connector 
Transmission 
method 
High-speed RS-485 
Transmission  cable 
Shielded  twisted  pair  cable 
Electrical  isolation 
500V DC 
Communication 
Message  type 
Loop-type  data  exchange 
Equipment ID 
0AFE (hex) 
Serial transmission 
speed  supported 
(auto-detection) 
9.6kbps; 19.2kbps; 93.75kbps; 187.5kbps; 500kbps; 1.5Mbps; 3Mbps; 6Mbps; 
12Mbps (bits per second) 
Environment 
Standards 
IEC 61131-2,UL508 
Storage/operation 
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity) 
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity),  pollution  degree 2 
Shock/vibration 
immunity 
International  standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 
68-2-27 (TEST Ea) 
Interference 
immunity 
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1000MHz, 1.4GHz ~ 2GHz, 10V/m 
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
Certificates
 
CE, UL
 
 Components 
 PROFIBUS DP Connector 
To connect to PROFIBUS DP network, use standard DP connector for the wiring. 
PIN 
PIN name 
Definition 
Not  defined 
Not  defined 
Rxd/Txd-P 
Sending/receiving  data P(B) 
Not  defined 
DGND 
Data  reference  potential 
VP 
Power  voltage - positive
 
Not  defined 
Rxd/Txd-N 
Sending/receiving  data N(A) 
Not  defined 
1
6
5
9
 
 Address Setup Rotary Switch 
The two rotary address setup switches set up the node addresses on 
PROFIBUS DP network in  hexadecimal form.  Setup range: 0x01 ~ 0x7D (0 or 
0x7E ~ 0xFF are  forbidden). 
Rotary switch 
x 16
1
 
x 16
0
 
Multiple 
× 16 
× 1 
 
N
O
D
E
A
D
D
R
E
S
S
x1 6
0
x1 6
1
 
Example: If you need to set the node address of DVPPF02-H2 as 26 (1A Hex), simply switch the 
corresponding rotary switch of x16
1
 to “1" and the corresponding rotary switch of x16
0
 to”A”. 
Switch setting 
Description 
0x01 ~ 0x7D 
Valid PROFIBUS DP address 
0 or 0x7E ~ 0xFF 
Invalid PROFIBUS DP address 
Note: 
The changed values on switches are 
only valid when DVPPF02-H2 is re-powered. 
When DVPPF02-H2 is operating, changing 
the set value of the address will be regarded 
invalid.
 
 Extension Port 
The extension  port  on DVPPF02-H2 is used for the connection to the next DVPPF02-H2 or  extension 
modules of DVP-EH2 series PLC MPU. 
 Basic Operation 
 Connecting DVPPF02-H2 to DVP-EH2 Series PLC MPU 
S TO P
R UN
0
1
 
IN
O UT
PO WER
R UN
ER RO R
BAT .L OW
DVP - 2 0E H
x16
0
x16
1
 
Switch off DVP-EH2. Open the connection 
port on the right hand side of DVP-EH2 and 
connect DVPPF02-H2 to DVP-EH2. Switch 
on DVP-EH2, and DVP-EH2 will supply 
power to DVPPF02-H2. There is no need to 
connect DVPPF02-H2 to an external power 
supply.
 
 Installing DVP-EH2 and DVPPF02-H2 on DIN Rail 
x16
0
x16
1
STO P
R UN
0
1
 
IN
OUT
PO WER
RUN
ERR OR
BAT.LO W
DVP-20EH
 
1.  Use 35mm DIN rail. 
2.  Open the DIN rail clips on DVP-EH2 and 
DVPPF02-H2. Insert DVP-EH2 and 
DVPPF02-H2 on the DIN rail.   
3.  Clip up the DIN rail clips on DVP-EH2 
and DVPPF02-H2 to fix DVP-EH2 and 
DVPPF02-H2 on the DIN rail.   
 
 Connecting to PROFIBUS DP Connector 
 
Insert the PROFIBUS DP bus connector into 
the PROFIBUS DP connector on 
DVPPF02-H2. Screw it tight to ensure 
DVPPF02-H2 and the PROFIBUS DP bus 
are  properly  connected. 
 Installation & Wiring 
1.  Install DVPPF02-H2 in an enclosure with sufficient 
space around it to allow heat dissipation (see the 
figure). 
2.  DO NOT place the I/O signal wires and power 
supply wire in the same wiring circuit. 
D>50mm
PF02- H2
D
D
D
D
D
D
E 2 PLC
H
 
 Control Register 
The control registers (CR) are the registers inside DVPPF02-H2. See the table below for the definitions of 
all the CRs. DVP-EH2 series PLC MPU can read or write the CR allowed through DFROM/DTO 
instructions. 
CR# 
Attribute 
Content 
High  byte 
Low  byte 
#0 
Read 
Model name 
DVPPF02-H2 model  code = H
0250 
#1 
Read 
Firmware  version 
Displaying the current firmware version in hex, e.g. 
V1.00 is indicated  as H’0100. 
#2 
Read 
Length of I/O data 
Length of output I/O data  Length of input I/O data 
#3 ~ #102 
Write/read 
Input  data  mapping 
Area for storing data from DVPPF02-H2 to 
PROFIBUS DP master 
#103 ~ #202 
Read 
Output  data 
mapping 
Area for storing data from PROFIBUS DP master to 
DVPPF02-H2. 
#203 ~ #206 
Set up by the system. DO NOT use it. 
#207 ~ #250 
Reserved 
#251 
Read 
Error 
Register for storing  errors. See 
 for  error  codes. 
#252 ~ #383 
Reserved 
#384 ~ #511 
Set up by the system. DO NOT use it. 
 LED Indicators & Trouble-Shooting 
There are 2 LED indicators on DVPPF02-H2. POWER indicator displays the status of the working power. 
NET indicator displays the connection status of the communication. 
 POWER LED 
LED status 
Indication 
How to deal with it? 
Green light on 
The power is normal. 
-- 
Off 
No  power 
1. Check if the power of DVP-EH2 is normal. 
2. Check if the connection between DVPPF02-H2 
and DVP-EH2 is normal. 
 NET LED 
LED status 
Indication 
How to deal with it? 
Off 
No  power 
1. Check if the power of DVP-EH2 is normal 
2. Check if the connection between DVPPF02-H2 
and DVP-EH2 is normal 
Red light on 
DVPPF02 is operating but is 
not connected to PROFIBUS 
DP bus. 
Check if DVPPF02-H2 is normally  connected to 
PROFIBUS DP bus. 
Red  light 
flashes 
Depending  on  the value in 
CR#251 
See the error code table for how to deal with it. 
Green light  on 
DVPPF02-H2 is in data 
exchange  status. 
-- 
 Error Codes 
Code 
Description 
How to deal with it? 
00 
DVPPF02-H2  operates  normally. 
-- 
01 
Hardware  error 
Send your DVPPF02-H2 back to the factory for 
repair. 
02 
PROFIBUS DP watch  dog error 
Check if DVPPF02-H2 is normally  connected to 
PROFIBUS DP bus. 
03 
Address setup error (0, or exceeding 
0x01 ~ 0x7D) 
Set the address within the range 0x01 ~ 0x7D and 
re-power  DVP-EH2. 
04 
24V low  voltage  error 
Check if the power voltage of DVP-EH2 is normal; 
check if DVPPF02-H2 is normally connected to 
DVP-EH2. 
05 
5V low  voltage  error 
Send your DVPPF02-H2 back to the factory for 
repair. 
 
 
注意事項 
 
使用前請務必仔細閱讀本使用手冊,並依照本手冊指示進行操作,以免造成產品受損或人員受傷。 
 
配線時請務必關閉電源。 
 
本使用說明書僅提供電氣規格、功能規格、安裝配線、故障排除及周邊裝置部分說明,本使用說明書僅
作為 DVPPF02-H2 操作指南和入門參考,PROFIBUS DP 協定的詳細內容這裏不作介紹。如果讀者想瞭
解更多 PROFIBUS DP 協定的內容,請參閱相關專業文章或書籍資料。 
 
本機為開放型機殼,因此使用者使用本機時,必須將其安裝於具防塵、防潮及免於電擊∕衝擊意外的外
殼配線箱內。另必須具備保護措施(如:特殊的工具或鑰匙才可打開),防止非維護人員操作或意外衝
擊本體,造成危險及損壞。 
 
本產品用來控制運轉中的機械及設備。為避免損壞本產品,只有合格且熟悉本產品結構及操作的專業人
員才可進行本產品的安裝、操作、配線及維護。 
 
交流輸入電源不可連接於輸入∕輸出信號端,否則可能造成嚴重損壞。請在上電前再次確認電源配線,
且請勿在上電時觸摸任何端子。本體上的接地端子    務必正確的接地,以提高產品抗雜訊能力。 
 
產品簡介 
謝謝您使用台達 DVPPF02-H2 網路通訊模組。DVPPF02-H2 定義為 PROFIBUS DP  通訊模組,可用於
PROFIBUS DP
網路與 DVP-EH2 系列 PLC 主機的連接,DVPPF02-H2 無需外接電源,與 DVP-EH2 主機連
接好後由 DVP-EH2 主機提供電源。 
 
功能特色
 
1. 
支持 DP 主站與多個從站之間的迴圈資料傳輸。 
2. 
在 PROFIBUS DP 網路配置工具中支援 GSD 文檔。 
3. 
在 PROFIBUS DP 網路配置工具中支援 4 槽  (slot)  配置。 
4. 
自動偵測通訊速率,最高通訊速率支援 12Mbps。 
5.  I/O
資料長度可通過 PROFIBUS DP 網路配置工具自由配置,輸入資料長度總和最大可配置 100 個 word,
(4 個 slot 配置長度之和),輸出資料長度總和最大可配置 100 個 word(4 個 slot 配置長度之和)。 
6. 
錯誤碼診斷功能。 
 
產品外觀及各部介紹 
 
82  [3.228]
9
0
  
[3
.5
4
3
]
40  [1.575]
7
  
[0
.2
7
6
]
PO WE R
NET
X
1 6
X
1 6
2
3
5
4
6
7
1
8
 
尺寸單位:mm 
 
1
擴充模組連接埠 
2
位址設定開關 
3 POWER LED
指示燈 
4 NET LED
指示燈 
5 PROFIBUS DP
通訊連接器 
6
擴充模組連接頭 
7 DIN
軌固定扣 
8 DIN
軌槽 
 
繁體中文 
 
功能規格 
PROFIBUS DP
連接器 
接頭 
DB9
接頭 
傳輸方式 
高速 RS-485 
傳輸電纜 
遮罩式雙絞線 
電氣隔離 
500V DC 
通訊 
資訊類型 
迴圈式資料交換. 
設備 ID 
0AFE (hex) 
支援串列傳輸速度 
(自動偵測) 
支持 9.6kbps; 19.2kbps; 93.75kbps; 187.5kbps; 500kbps; 1.5Mbps; 3Mbps; 6Mbps; 
12Mbps
(位元∕秒) 
環境規格 
標準 
IEC 61131-2,UL508 
標準 
操作∕儲存環境 
儲存:-25°C ~ 70°C(溫度),5 ~ 95%(濕度) 
操作:0°C ~ 55°C(溫度),50 ~ 95%(濕度),污染等級 2 
耐震動∕衝擊 
國際標準規範  IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 
(TEST Ea) 
雜訊免疫力 
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1000MHz, 1.4GHz ~ 2GHz, 10V/m 
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
認證專案
 
CE
認證、UL 認證
 
 
各部分元件介紹 
 PROFIBUS DP
通訊連接器 
與 PROFIBUS DP 網路連接時,使用標準 PROFIBUS DP 連接器進行配線。 
接腳 
名稱 
定義/說明 
未指定 
未指定 
Rxd/Txd-P 
接收∕發送資料 P (B) 
未指定 
DGND 
資料參考接地 
VP 
電源電壓-正壓
 
未指定 
Rxd/Txd-N 
接收∕發送資料 N (A) 
未指定 
1
6
5
9