Delta Electronics DOP-A/AE/AS Guía De Conexión

Descargar
Página de 137
Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
 
1-38  
Revision January, 2008, Doc. Name: 2007PDD23000007 
„
 
slot 0: X48 
„
 
slot 1: Y32 
„
 
slot 2: empty16 
„
 
Analog Type 
„
 
slot 3: X4W 
„
 
slot 4: Y4W 
3) Communication 
Protocol: 
External I/O (X, Y, WX, WY) 
y
 
Address rules:[r][u][s][n/b]. 
i) 
Word no/Bit no [n/b] 
ii) 
Slot number [s] 
iii) 
Unit number [u] 
iv) 
Remote number [r] 
„
 
Only support EH-150 
v) 
ex1: WX103 represents unit 1, word 3 of slot 0 
vi) 
ex2: X103 represents bit 3 of slot 1 
vii) 
ex3: X113 represents bit 13 of slot 1 
viii) 
ex4: Y2004 represents unit 2, bit 4 of slot 0 
ix) 
ex5: Y2104 represents unit 2, bit 4 of slot 1 
y
 
External I/O (X, Y, WX, WY) cannot read and write several addresses one time so they do not 
support “optimum read/write” characteristic. 
Internal Output 
y
 
Shared Internal Output (M, WM) read and write the same address. For example,  
i) 
M3ab and WM3a: the read and write address of M3ab is the bit b of WM3a. 
y
 
CPU Link Area (L, WL) are the same as Shared Internal Output (M, WM). CPU Link Area (L, WL) 
also read and write the same address. 
i) Only 
support 
EH-150. 
C. Connections (Connector Pinouts) 
RS-232 
DOP Series 
9 pin D-SUB male (RS-232) 
Controller 
9 pin D-SUB male (RS-232) 
Controller 
9 pin D-SUB male (RS-232)
RXD (2)
( 5)  SD1
TXD (3)
GND (5)
(6) R D1
(1) SG1
RTS (7)
(7) DR1
CT S (8 )
(8 ) RS1
 
 
 
 
 
 
 
Top View 
Pin1