Delta Electronics DOP-A/AE/AS Guía De Conexión

Descargar
Página de 137
Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series 
Revision January, 2008, Doc. Name: 2007PDD23000007 
 
 
1-63 
LG XGT CNET 
A. HMI factory settings 
Baud rate: 9600, 8, None, 1. 
Controller station number: 0. 
Control area/status area: DW0 / DW10. 
NOTE
  
1)  HMI default setting is predefined for XGL-CH2A CNET communication module. 
B. Definition of controller Read/Write address 
Registers 
Register Type 
Format 
Word No. 
Bit No. 
Data Size 
I/O Relay 
PWn 
n: 0 ~ 2047 
N/A 
Word 
Auxiliary Relay 
MWn 
n: 0 ~ 2047 
N/A 
Word 
Keep Relay 
KWn 
n: 0 ~ 2047 
N/A 
Word 
Link Relay 
LWn 
n: 0 ~ 11263 
N/A 
Word 
Special Relay 
FWn 
n: 0 ~ 2047 
N/A 
Word (Read Only) 
Timer Elapsed Value 
TWn 
n: 0 ~ 2047 
N/A 
Word 
Counter Elapsed Value 
CWn 
n: 0 ~ 2047 
N/A 
Word 
Data Register 
DWn 
n: 0 ~ 32767 
N/A 
Word 
Contacts 
Contact type 
Format 
Word No. 
Bit No. 
I/O Relay 
PXnb 
n: 0 ~ 2047 
b: 0 ~ F 
Auxiliary Relay 
MXnb 
n: 0 ~ 2047 
b: 0 ~ F 
Keep Relay 
KXnb 
n: 0 ~ 2047 
b: 0 ~ F 
Link Relay 
LXnb 
n: 0 ~ 11263 
b: 0 ~ F 
Special Relay 
FXnb 
n: 0 ~ 2047 
b: 0 ~ F 
Timer Contact Relay 
TXb 
N/A 
b: 0 ~ 2047 
Counter Contact Relay 
CXb 
N/A 
b: 0 ~ 2047 
Data Relay 
DXn.b 
n: 0 ~ 32767 
b: 0 ~ F