Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
 
1-86  
Revision January, 2008, Doc. Name: 2007PDD23000007 
Mitsubishi FX Series PLC via Computer Link 
A. HMI factory settings 
Baud rate: 9600, 7, EVEN, 1. 
Controller Station number: 0. 
Control area/status area: D0 / D10. 
NOTE
 
1)  This communication protocol supports FX series RS485 and RS232 communication module. 
2)  The default setting of this communication protocol is to support RS485 communication module. If the 
user needs to use RS232 communication module, the user must change the communication setting from 
RS485 to RS232 manually. 
3)  For more detailed information regarding the communication setting method, please refer to Mitsubishi 
Communication User Manual named “User’s Manual - Data Communication Edition”. 
B. Definition of controller Read/Write address 
Registers 
Read/Write Range 
Register Type 
Format 
Word No. 
Bit No. 
Data length 
Auxiliary Relay 
Mn 
n: 0-7679 
N/A 
Word 
Special Auxiliary Relay 
Mn 
n: 8000-8511 
N/A 
Word 
Status Relay 
Sn 
n: 0-4095 
N/A 
Word 
Input Relay 
Xn 
n: 0-377(octal) 
N/A 
Word 
Output Relay 
Yn 
n: 0-377(octal) 
N/A 
Word 
Timer PV 
Tn 
n: 0-255 
N/A 
Word 
16-bit Counter PV 
Cn 
n: 0-199 
N/A 
Word 
32-bit Counter PV 
Cn 
n: 200-255 
N/A 
Double Word 
Data Register 
Dn 
n: 0-7999 
N/A 
Word 
Special Data Register 
Dn 
n: 8000-8511 
N/A 
Word 
¾
  Auxiliary Relay / Special Auxiliary Relay / Status Relay / Input Relay / Output Relay: Address must be 
the multiple of 16. 
Contacts 
Read/Write Range 
Contact type 
Format 
Word No. 
Bit No. 
Auxiliary Relay 
Mn 
N/A 
n: 0-7679 
Special Auxiliary Relay 
Mn 
N/A 
n: 8000-8511 
Status Relay 
Sn 
N/A 
n: 0-4095