Operation 
Front Panel Display and Controls 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
General Operation 
Once the AGMSZ has been installed, set up, and powered ON, the monitor will make measurements in the 
area being sampled for ammonia gas without further operator intervention. The results of those 
measurements are shown on the front panel display.  
 
 
 
In the example shown above, MEASURE indicates that the AGMSZ is actively monitoring for refrigerant 
gas, and that currently 45 ppm of R-717 (ammonia gas) is being detected. This display also indicates that a 
peak measurement of 485 ppm has been made.  
An operator can reset the peak value to zero by pressing the ENTER button. 
A log of up to 200 previous measurements can be viewed using the PPM LOG function (Page 15). 
If the detected gas level exceeds the preset Leak, Spill, or Evacuate alarm point, then the monitor 
responds by turning ON the front panel ALARM (red) light and energizing the corresponding alarm relay. 
If the internal audible alarm is turned ON, it too will activate (AUDALRM page 16). Optional external 
alarm devices can be connected to the alarm relays to alert personnel that a Leak, Spill, or Evacuate alarm 
condition has occurred (Page 10). Pressing the front panel SILENCE button will acknowledge an alarm 
and turn OFF all alarm indicators with the exception of the front panel ALARM light. The alarm circuit 
will reactivate, however, if the alarm condition is not cleared within the time period set by the SILENCE 
function (Page 17). The ALARM light will turn OFF after the detected gas level goes below the lowest 
alarm point and after the SILENCE button is pressed. 
MEASURE  00485pk 
   45ppm R717 
Display 
Screen 
ENTER 
Press this button to: 
1) Clear peak reading 
2) Save a function 
screen’s displayed value 
Keypad 
Use these buttons to: 
1)  Enter function mode and 
then move arrow (>) on 
screen to the desired function 
2) Scroll through data 
3) Change a function’s value 
MONITOR ON 
Light (Green) 
1) Flashes 
during warm-up 
2) Lights steady 
during normal 
operation 
SYSTEM FAULT 
Light (Yellow)  
Flashes when 
any one or more 
of the faults 
listed on Page 
19 occur 
ALARM Light 
(Red)  
Flashes when 
the detected gas 
level exceeds 
any of three 
preset alarm 
points 
SILENCE / QUIT 
Press this button to: 
1) Acknowledge a 
system fault or gas 
alarm by turning OFF 
the internal audible 
alarm and de-energizing 
the corresponding 
fault/alarm relay 
2) Return to the previous 
screen without saving 
data when in the 
function mode