STRYKER VAV USER GUIDE
25
62-2030—01
16. SENSOR CALIBRATION
Use this page for sensor calibration in an Stryker VAV device on the LON network. Using Sensor Calibration feature, you can 
correct the input values to the controller. This action can be performed with the device in online mode. The controller must be in a 
commissioned state. While performing Sensor Calibration, the device should not be used by another application. You can 
calibrate only analog inputs to the controllers.
To calibrate:
16.1 Fields
Table 15. Sensor Calibration Fields.
Tip
To clear the Offset value for any of the configured 
sensors:
Calculate the calibrated value using the below formula, type it 
in the Calibrated value field and click Calibrate.
Calibrated Value = Actual Value - Old Offset Value
For Example:
If the configured Sylk bus sensor reads the room temperature 
as 79.88 F and you want to calibrate it to 85.5 F. By mistake if 
you type the calibrated value as 855 F, the offset value will be 
calculated as 775.102 F. This will display the Actual value as -
324.742 which is abnormal.
If you find any abnormal value like this and you want to clear 
the offset value. Calculate the Calibrated value as shown 
below and type the calculated value in the Calibrated Value 
field.
In this case
The Actual value = -324.742
Old Offset value = 775.102
Calibrated Value = Actual Value - Old Offset Value
                            = -324.742-775.102
                             = -1099.844 F
If you type this value in the Calibrated Value field and click 
Calibrate, the Offset value will be cleared.
RELATED TOPICS
Step
Action
1
From the 
Nav menu, choose Station > Driver > LON network > AscLonVAV device.
2
Right-click the device and choose 
Views > Sensor Calibration from device items. The Sensor 
Calibration screen appears.
3
Enter information in the available fields.
4
Click 
Refresh to refresh the settings.
5
Click 
Calibrate to calibrate settings.
Name
Definition
Sensor Name
Displays the sensor names.
Actual Value
Displays the current value of the sensor as read by the controller.
Calibrated Value
Enter the calibrated value.
Offset Value
Once you click 
Calibrate, the offset value appears. Offset value is a difference between 
Actual value and Calibrated value.