Model BCSW-FRP
CAUTION
When installing a fan, ensure the proper protective 
devices are used to protect personnel from 
moving parts and other hazards. A complete 
line of protective accessories are available from 
Greenheck including belt guards, shaft guards, and 
electrical disconnects.
Electrical Disconnects
All fan motors should have disconnects located in 
close visual proximity to turn off electrical service. 
Service disconnects shall be locked out when 
maintenance is being performed.
Moving Parts
All moving parts must have guards to protect 
personnel. Refer to local codes for requirements 
as to the number, type and design. Fully secure fan 
wheel before performing any maintenance. The fan 
wheel may start “free wheeling” even if all electrical 
power has been disconnected. Before the initial 
start-up or any restart, check the belt and shaft 
guards and the access doors to ensure that they 
are installed and secure.
Table of Contents
General Information
 Receiving. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
 Handling  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
 Storage  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation Recommendations
 BCSW-FRP  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
 Bases. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
  Belt Guards  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
  Drain Connections  . . . . . . . . . . . . . . . . . . . . . . . . . 5
  Ductwork / Stacks. . . . . . . . . . . . . . . . . . . . . . . . . . 5
  Rotatable Housing  . . . . . . . . . . . . . . . . . . . . . . . . . 5
 Radial gap, overlap & wheel alignment . . . . . . . . . 6
Flexible Couplings  . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
V-Belt Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Unit Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Vibration  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Routine Maintenance . . . . . . . . . . . . . . . . . . . . . .  9-10
 Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
  Shaft Bearings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
  V-Belt Drive  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Unit Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Troubleshooting  . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Maintenance Log  . . . . . . . . . . . . . . . . . . . .  Backcover
Warranty  . . . . . . . . . . . . . . . . . . . . . . . . . . . Backcover
Machined parts coated with rust preventive should be 
restored to good condition promptly if signs of rust occur. 
Immediately remove the original rust preventive coating 
with petroleum solvent and clean with lint-free cloths. 
Polish any remaining rust from surface with crocus cloth 
or fine emery paper and oil. Do not destroy the continuity 
of the surfaces. Wipe clean thoroughly with Tectyl
®
 506 
(Ashland Inc.) or the equivalent. For hard to reach internal 
surfaces or for occasional use, consider using Tectyl
®
 
511M Rust Preventive or WD-40
®
 or the equivalent.