D9412GV3/D7412GV3 | Operation and Installation Guide | 8.0  
On-Board Points 
 
Bosch Security Systems, Inc. | 10/10 | F01U143070-03 
32
 
8.3 Point 
Parameters 
The condition of on-board Points 1 to 8 is determined 
by measuring the voltage across the point input 
terminal and one of the common terminals. The 
sensor loops must be connected and the 1 kΩ EOL 
resistor in place. 
Table 9: 
Point Parameters 
 
Loop Voltage 
Range 
Open 
Greater than 3.7 VDC, but less than 5.0 
VDC. 
Normal 
Greater than 2.0 VDC, but less than 3.0 
VDC. 
Shorted 
Greater than 0.0 VDC, but less than 1.3 
VDC. 
 
 
Figure 13:  On-board Point Sensor Loop Wiring 
1 k
4
5
6
9
7
10
1
2
3
2
3
2
8
9
10
 
1 -  100 Ω maximum 
2 -  Point input terminal 
3 -  Common 
4 -  Normally-closed contacts (NC)* 
5 -  Normally-open contacts (NO) 
6-  Combination: Normally-open contacts and 
normally-closed contacts (NO/NC) 
7 -  P105F (Package of 8 EOL resistors) or 
P105BL (Package of 8 UL Listed EOL 
resistors) (P/N: 15093130-004) 
8 -  Brown 
9 -  Black 
10 -  Red
 
*  UL does not allow normally-closed loops for commercial fire applications.