D9412GV3/D7412GV3 | Operation and Installation Guide | 9.0  
Off-Board Points 
 
Bosch Security Systems, Inc. | 10/10 | F01U143070-03 
48
 
Using Molex
®
 Connectors 
Each D8128D Module is supplied with a 30 cm (12 in.) female-to-female Molex cable assembly. 
P1 and P2 are Molex connectors that parallel the COM, IN, OUT, and +12.0 VDC terminals on the terminal 
strip. In installations with multiple D8128Ds, use these connectors (as opposed to terminals) with the supplied 
cable; however, when connecting D8128D Modules directly to the control panel, the terminal strip is easier to 
use. 
The Molex connectors provided are "keyed" (Molex plug can fit in only one direction). Ensure that the connector 
is attached correctly: the red wire is on the bottom of P1 (or P2) and the black wire is on the top. 
When connecting multiple D8128Ds to a control panel, you can connect the control panel terminals to P1 or the 
COM, IN, OUT, and +12V terminals on the first D8128D. Then connect P2 of the first D8128D to P1 of the 
second D8128D and so on (Figure 22). 
Figure 22:  Wiring Multiple D8128Ds Using Molex
®
 Connectors 
COM IN OUT+12V
P1
P2
COM IN OUT+12V
P1
P2
28
27
26
25
24
23
COM IN OUT+12V
P1
P2
1
2
3
4
5
6
7
8
9
1 -  D9412GV3 Control Panel 
2 -  Yellow 
3 -  Green 
4 -  Black 
5- Red 
6 -  First D8128D 
7 -  Second D8128D 
8 -  Third 8128D 
9-  Up to 15 per Zonex Bus