11.0 Arming Devices 
11.1 Description 
Keypads, maintained or momentary contact 
keyswitches, or a combination of the two are used to 
arm and disarm areas. The D9412GV3 can support 
up to 32 areas. The D7412GV3 can support up to 8 
areas. Refer to 3.3.5 Areas and Accounts on page 12 
for a description of areas. 
 
For UL 864 Commercial Fire applications, 
refer to Installing Combination Fire and 
Intrusion Alarm Systems
 in the 
D9412GV3/D7412GV3 Approved 
Applications Compliance Guide
  
(P/N: F01U143069) for important 
information about combination fire and 
intrusion systems. 
11.2  Keypad Terminals 29 to 32 
The Bosch Security Systems, Inc. keypad is a four-
wire powered device used to arm and disarm areas, 
annunciate complete system status, initiate system 
tests, and control many functions of the security 
system.  
The system can supervise up to 16 keypads. The 
control panel sends a Serial Device Trouble Report, 
SDI FAILURE, in the Modem IIIa
2
 format or 
Expansion Module Failure (333) in Contact ID format, 
if it loses communication with a supervised keypad. 
CALL FOR SERVICE appears in any keypad that 
loses communication with the control panel, if the 
keypad has text display capability. SERVC KEYPAD 
appears at all other keypads connected to the system.  
A total of 32 unsupervised keypads can be connected 
to the system. The number of supervised keypads, 
number of areas, and the available power affect the 
total number of keypads that can be connected to the 
system. Refer to Keypad in the 
D9412GV3/D7412GV3 Program Entry Guide 
(P/N: F01U170807) for complete programming details 
on keypad options.  
Five types of keypads are available for use with the 
system.  
  D1255/D1255B/D1255RB: 16-character 
alphanumeric display for general use. 
Addressable to all 16 SDI addresses. 
  D1256/D1256RB: Text display keypad with keys 
designated for local fire alarm control. 
Addressable to all 16 SDI addresses. 
  D1257/D1257RB: Text display keypad for fire 
annunciation. Addressable to all 16 SDI 
addresses. 
  D1260/D1260B: Easy-to-read, 4-line by 20-
character LCD display with eight “soft” keys to 
display simple selections. Addressable SDI 
Addresses 1-8.  
  D720/D720B: LED display keypad appropriate for 
use as a single area keypad with up to eight 
points. Addressable to all 16 SDI addresses. 
 
 
D1255 and D720 are available in white 
(D1255W and D720W) or red (D1255R 
and D720R). 
 
 
To meet UL 864 requirements for 
Commercial Fire applications, use a 
D1255RB, D1256RB, or D1257RB for a 
fire keypad or fire annunciator. 
For operational information, refer to the user’s guide 
for the specific keypad.  
11.2.1  Assigning an Address for the Keypad 
Switches on the keypad assign an address (1 to 16). 
The address determines if the keypad is supervised, 
the scope of the keypad, and to what area the keypad 
is assigned. Refer to Keypad Assignment in the 
D9412GV3/D7412GV3 Program Entry Guide 
(P/N: F01U170807) for a complete description of 
addresses. 
Table 19 shows the correct switch setting for each 
address. 
Table 19:  Keypad Address Settings 
 
Switch 
Address 
1 2 3 4 5 6 
Address #1 
ON 
ON 
ON 
ON 
ON 
Address #2 
OFF  ON 
ON 
ON 
ON 
Address #3 
ON 
OFF  ON 
ON 
ON 
Address #4 
OFF  OFF  ON 
ON 
ON 
Address #5 
ON 
ON 
OFF  ON 
ON 
Address 
#6  OFF ON  OFF ON 
ON 
Address #7 
ON 
OFF  OFF  ON 
ON 
Address 
#8  OFF OFF OFF ON 
ON 
Address #9 
ON 
ON 
ON 
OFF 
ON 
Address #10  OFF  ON ON OFF 
ON 
Address #11  ON 
OFF  ON 
OFF 
ON 
Address #12  OFF  OFF  ON 
OFF 
ON 
Address #13  ON 
ON 
OFF  OFF 
ON 
Address 
#14 OFF ON  OFF OFF 
ON 
Address #15  ON 
OFF  OFF  OFF 
ON 
Address 
#16 OFF OFF OFF OFF 
Encod
ing  
T
one ON/OF
F
 
ON