ARI* CAPACITY RATINGS — 581B036-150
                         LEGEND
*Air-Conditioning & Refrigeration Institute.
†Applies only to units with capacity of 65,000 Btuh or less.
**The IPLV is not applicable to single-compressor units.
NOTES:
1. Rated in accordance with ARI Standard 210/240 (036-120 units) or
360 (150 units) and 270 (036-150 units).
2. Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:
Cooling Standard: 80 F db, 67 wb indoor entering-air temperature
and 95 F db outdoor entering-air temperature.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature
and 80 F db outdoor entering-air temperature.
3. All 581C024-060 and 581B036-150 units are in compliance with
ASHRAE 90.1-1999 Energy Standard for minimum SEER and EER
requirements. Refer to state and local codes or visit the following
website: http://bcap-energy.org to determine if compliance with this
standard pertains to a given geographical area of the United States.
4. All 581C024-060 and 581B036-120 units are Energy Star certified.
HEATING CAPACITIES AND EFFICIENCIES — 581B036-150
208/230-1-60 — SINGLE-STAGE GAS HEAT
LEGEND
AFUE — Annual Fuel Utilization Efficiency.
208/230-1-60 — SINGLE-STAGE GAS HEAT — LOW NOx
LEGEND
AFUE — Annual Fuel Utilization Efficiency.
UNIT
581B
NOMINAL
TONS
COOLING
(Btuh)
TOTAL
kW
SEER†
EER
SOUND RATING
dB
IPLV
036
3
36,000
3.21
13.0
11.20
76
**
048
4
46,000
4.25
13.0
11.05
76
**
060
5
61,000
5.55
13.0
11.00
80
**
072
6
73,000
6.70
11.00
80
**
090
7
1
/
2
90,000
8.18
11.00
82
11.6
102
8
1
/
2
103,000
8.90
11.60
82
12.8
120
10
120,000
10.91
11.00
84
11.4
150
12
1
/
2
138,000
14.40
9.6
86
10.3
EER
— Energy Efficiency Ratio
IPLV
— Integrated Part-Load Value
SEER — Seasonal Energy Efficiency Ratio
Sizes 036-120
Only
Sizes 150
Only
UNIT
581B
INPUT CAPACITY
OUTPUT CAPACITY
TEMPERATURE
RISE (°F)
MINIMUM HEATING
AIRFLOW (CFM)
EFFICIENCY
AFUE (%)
Steady State (%)
036072
72,000
58,000
25-55
1004
82.8
82.0
036115
115,000
90,000
55-85
1002
80.0
80.0
048072
72,000
58,000
25-55
1004
82.8
82.0
048115
115,000
90,000
35-65
1320
81.0
81.0
048150
150,000
118,000
50-80
1396
80.4
80.0
060072
72,000
58,000
25-55
1004
82.8
82.0
060115
115,000
92,000
35-65
1327
81.0
81.0
060150
150,000
118,000
50-80
1314
80.4
80.0
UNIT
581B
INPUT CAPACITY
OUTPUT CAPACITY
TEMPERATURE
RISE (°F)
MINIMUM HEATING
AIRFLOW (CFM)
EFFICIENCY
AFUE (%)
Steady State (%)
036060N
60,000
50,000
20-50
930
80.2
81.2
036090N
90,000
74,000
30-60
1150
81.0
81.4
048060N
60,000
50,000
20-50
930
80.2
81.2
048090N
90,000
74,000
30-60
1150
81.0
81.4
048120N
120,000
101,000
40-70
1340
80.7
82.4
060060N
60,000
50,000
20-50
930
80.2
81.2
060090N
90,000
74,000
30-60
1150
81.0
81.4
060120N
120,000
101,000
40-70
1340
80.7
82.4