Bryant 581C Manual De Usuario

Descargar
Página de 298
148
PHYSICAL DATA — 581C
LEGEND
UNIT SIZE 581C 
024
036
048
060
NOMINAL CAPACITY (tons)
OPERATING WEIGHT(lb) 
  Base Unit** 
530 
540 560 
635 
COMPRESSOR 
Scroll
  Quantity 
1 1 
  Oil (oz) 
25 42 
56 
53 
REFRIGERANT TYPE 
R-22
Expansion Device Operating Charge (lb-oz) 
Acutrol™ MeteringDevice
  Standard Unit 
5---3 
7---11
8---8 
12---11
  Unit With Perfect Humidity Adaptive Dehumidification System 
10---2
14---0
14---13
21---0
CONDENSER FAN
Propeller
  Quantity...Diameter (in.) 
1...22
1...22
1...22
1...22
  Nominal Cfm 
3000
3500
3500
4100
  Motor Hp...Rpm
1/8...825
1/8...825
1/8...825
1
/
4
...1100
  Watts Input (Total) 
180
180
180
320
CONDENSER COIL
Enhanced Copper Tubes, Aluminum LancedFins
  Rows...Fins/in.
1...17
1...17
2...17
2...17
  Total Face Area (sq ft) 
14.6
14.6
16.5
16.5
EVAPORATOR COIL
Enhanced Copper Tubes, Aluminum Double-Wavy Fins
  Standard Unit 
    Rows...Fins/in. 
2...15
2...15
2...15
4...15
    Total Face Area (sq ft) 
4.2
5.5
5.5
5.5
   Perfect Humidity Coil Adaptive Dehumidification System 
    Rows...Fins/in. 
1...17
1...17
2...17
2...17
    Total Face Area (sq ft) 
3.5
3.9
3.9
3.9
EVAPORATOR FAN
Centrifugal Type, Belt Drive
  Quantity...Size (in.) 
1...10 x 10
1...10 x 10
1...10 x 10
1...10 x 10
  Nominal Cfm 
800
1200
1600
2000
  Maximum Continuous Bhp 
Std
0.58
1.20
1.20
1.30/2.40* 
Hi-Static
2.40
2.40
2.40
2.90
  Motor Frame Size
Std
48
48
48
48/56†
Hi-Static
56
56
56
  Motor Rpm 
Std
1620
1620
1620
1725
Hi-Static
1725
1725
1725
  Fan Rpm Range 
Std
400-1000
680-1044
770-1185
1035-1460
Hi-Static
1075-1455
1075-1455
1300-1685
  Motor Bearing Type
Ball
Ball
Ball
Ball
  Maximum Fan Rpm 
1620
2100
2100
2100
  Motor Pulley Pitch Diameter A/B (in.)
Std
2.4/3.2
1.9/2.9
1.9/2.0
2.4/3.4
Hi-Static
2.8/3.8
2.8/3.8
3.4/4.4
  Nominal Motor Shaft Diameter (in.)
Std
5
/
8
1
/
2
1
/
2
5
/
8
Hi-Static
7/8
5
/
8
5
/
8
5
/
8
  Fan Pulley Pitch Diameter (in.) 
Std
4.0
4.5
4.0
4.0
Hi-Static
4.5
4.5
4.0
4.5
  Belt — Type...Length (in.) 
Std
1...A...36
1...A...36
1....4...36
1...A...40
Hi-Static
1...A...39
1...A...39
1...A...39
1...A...40
  Pulley Center Line Distance (in.) 
10.0 -12.4
10.0-12.4
10.0-12.4
14.7-15.5
  Speed Change per Full Turn of Movable Pulley Flange 
(rpm)
Std
60
65
70
75
Hi-Static
65
65
60
  Movable Pulley Maximum Full Turns from Closed 
Position
Std
5
5
5
6
Hi-Static
6
6
5
  Factory Setting — Full Turns Open 
Std
3
3
3
3
Hi-Static
31/2
31/2
31/2
  Factory Speed Setting(rpm) 
Std
756
826
936
1248
Hi-Static
1233
1233
1396
  Fan Shaft Diameter at Pulley (in.) 
5/8
5/8
5/8
5/8
Bhp — Brake Horsepower
*Single/three phase. 
**Base unit weight does not include any options or accessories. See Options and
Accessory weight tables for additional weight information.
†Indicates automatic reset.
58
1C02
4-
060